There are a number of ways to specify the addresses of registers in the slave device. SmartSwarm 351 uses the
convention of a base register type (Coil, Status, Input or Holding) and an offset, starting from zero, within that
register type. Hence, a register defined within SmartSwarm 351 as ‘Holding Register 5) might appear in other
manufacturers data as register 40,006, or 400,006.
SmartSwarm 351 decodes information exchanged using the following Modbus commands:
Function Code
Description
01
Read Coil Status
02
Read Input Status
03
Read Holding registers
04
Read Input registers
05
Force Single Coil*
06
Preset Single register*
15
Force multiple Coils*
16
Preset multiple registers*
22
Mask Write 4X register*
23
Read/Write 4X registers*
Table 51. Supported Modbus commands