SETPOINT TEMPERATURE CONTROLS

DST-7772

INSTALLATION AND OPERATING INSTRUCTIONS

§

Easy-to-Read Dual Digital Display with backlit which provides 
constant  readout  of  sensor  temperature  and  setpoint 
simultaneously, functional status and control settings. It also 
allows precise setpoint and differential settings 

§

Wide adjustable setpoint with temperature range from -40 to 
240°F and differential from 1 to 100°F. This enables the user to 
optimize  the  system  performance  for  any  applications.  A 
tighter  differential  can  be  achieved  (eg.  1°F  or  1°C)  than 
conventional electromechanical controls 

§

LED indicates output relay status

FEATURES

§

EEPROM memory retains control settings in the event of a 
power failure

§

Reliable Digital Electronic Accuracy 

§

Remote temperature sensor which can be extended to 500 ft. 

§

Adjustable Anti-Short Cycle Delay to ensure the output relay 
remains  off  for  up  to  20  minutes.  This  would  avoid 
unnecessary hard start and equipment wear 

§

Maximum and minimum memory for sensor temperature

§

Simple  and  user-friendly  programming  of  setpoint 

temperature, differential and cooling/heating modes 

§

Easy installation and setup

§

Selectable Fahrenheit or Celsius  scales

§

Selectable Heat or Cool modes

§

DST-7772can  handle  one  or  two  sensor  inputs  with  two 
setpoints. When using two sensor inputs, each setpoint can 
be corresponding to one relay output. (two single stage units 
in one control)

§

Lockout  mode  to  prevent  tempering  by  unauthorized 
personnel 

§

Sensor failure and out of range indication 

§

Fast  sampling  rate  (1  sec.)  Of  the  sensor  temperature  for 
instant control action

§

Easy-Connect Screwless Terminals for sensor connection

§

Backlit option: Auto (30 sec.)/OFF/ON

§

Power surge protection

The DST-777 is equipped with a Dual Digital display with backlit 

that  provides  a  constant  readout  of  the  sensor  temperature  and 
setpoint simultaneously as well as the other programmed settings. The 
front buttons allow the user to easily and accurately select the setpoint 
temperature,  differential  and  heating/cooling  mode  of  the  operation. 
This reliable and versatile control has a very wide setpoint range, an 
adjustable differential and time delay that makes it applicable in many 
different  applications.  The  single  stage  models  have  Pulse  Width 
Modulation  (PWM)  control  logic  to  prevent  overshoots  and 
undershoots in slow responding systems with large thermal mass such 
as pools or slabs. A sensor probe P-01 is supplied with the control. This 
solid state temperature sensor probe can be extended up to 500 feet.

DST-777 series controls are  microprocessor-based electronic 

one or two stage setpoint temperature controls, designed to provide 
one or two on/off controls (Single-Pole Double-Throw(SPDT) relay 
outputs) for residential/commercial heating, cooling, air conditioning 
and refrigeration applications. 

APPLICATION

Mount the DST-7772 controller to a suitable surface. Slotted keyholes and 
standard holes are provided for mounting purposes.

 

MOUNTING

SPECIFICATIONS

§

Setpoint 1 Temperature Range: -40 to 240°F(-40 to 116°C)

§

Setpoint 2 Temperature Range: -40 to 240°F(-40 to 116°C)

§

Differential 1 Adjustment: 1 to 100°F(1 to 38°C)

§

Differential 2 Adjustment: 1 to 100°F(1 to 38°C)

§

Anti-Short Cycle Delay 2: 0 to 20 min. (1-Minute increments)

§

Temperature Display Resolution: 0.1°F/0.1°C

§

Dimension: 

6 3/8”(W) x 6 5/8”(H) x 2 3/4”(D)

§

Weight: 3.0 lbs 

 

P-01 Sensor Probe:

§

Operating Voltage: 120 VAC, 50/60Hz 

,

Sheath: Copper 

,

Lead: 10” of 20 AWG heat resistence wire 

,

Dimension: 3/8" OD x 13/16" length 

,

Sensor: 10K ohm @ 77 F (25 C ± 1%) thermistor

°

°

,

Can be strapped on a pipe or inserted into a temperature well

,

Operating range: -60 to 255 F (-50 to 125 C) 

°

°

Models:

§

Enclosure: Flame Retardant Plastic 94V0

DST-7772  Two Stage Setpoint Temperature Control 

§

Anti-Short Cycle Delay 1: 0 to 20 min. (1-Minute increments)

§

Accuracy: ±1°C / ±1°F 

§

Input: 10K ohm thermistor probe(included): P-01 (designed 

for strap on a pipe or insert into a temperature well)

§

Temperature sampling rate: 1 second 

§

Relay: 1 or 2 x SPDT, 120VAC, Full Load 12A, 1Hp

CAUTION!

1.  To  prevent  electrical  shock  hazard,  disconnect  power  supply  before 

installing.

2.  All  wiring  must  comply  with  national  and  local  electrical  codes, 

ordinances, and regulations. 

4. 12-18 gauge wire is recommended for 120 VAC conections; 

5. This literature is provided for informational purposes only.

Never connect the load terminals to a load that takes more current than 
the amount listed for the relay in the electrical ratings. 

    18 gauge or larger wire is recommended for sensor connections.

3. Azel  Technologies is not responsible for damages resulting from misuse 

of its products. 

Note: Do not run sensor wires parallel to other electrical wiring or telephone 

wires. In case there is strong source of electromagnetic interference, 
twisted pair 20AWG wire is recommended. 

The sensor P-01 can be extended up to 500 with conventional 18 gauge 

wire(or larger to keep additional resistance to a minimum). It is designed to 
strap on a pipe or insert onto a temperature immersion well. 

MOUNTING THE SENSOR:

The sensor P-01 can also be insert onto a 3/8”(10mm) or ½”(12.7mm) 

ID temperature well.

Senors should be strapped to the pipe with cable tie. The flat side of the 

sensor should be resting on the pipe. In addition, they should be covered with 
a layer of insulation to minimize the effects of ambient temperature for a more 
reliable temperature reading.

Содержание DST-777 Series

Страница 1: ...essor based electronic one or two stage setpoint temperature controls designed to provide one or two on off controls Single Pole Double Throw SPDT relay outputs for residential commercial heating cooling air conditioning and refrigeration applications APPLICATION Mount the DST 7772 controller to a suitable surface Slotted keyholes and standard holes are provided for mounting purposes MOUNTING SPEC...

Страница 2: ...ned eg Stage 1 Heat Stage 2 Cool it is recommended to add a 3 F difference between the Heat setpoint and Cool setpoint temperature For example if Heat setpoint is set at 68 F and Cool setpoint should be set at 71 F When two sensor inputs are selected the control will operate as two single stage setpoint controls Sensor S1 controls relay 1 output and sensor S2 controls relay 2 output One or Two sen...

Страница 3: ...re Description The default value is F Stage 1 Differential Temperature Stage 1 Heating or Cooling Default setting is 1F Stage 1 Anti Short Cycle time delay Default is minutes 0 Default setting is 75F Default setting is H1 LCD Display 0 75f S i 8f i If H i Ac i 93 Down Key Up Key Reset Key Backlit Switch 2 Setpoint Temperature for 1 Sensor Input or Sensor 2 Temperature for 2 Sensor Input Sensor 1 T...

Страница 4: ...pen circuited or out of the lower range If not check for proper sensor operation by comparing it to a known ambient temperature The easiest way is to get an Azel Technologies DS 60P digital temperature gauge which displays two P 01 sensor temperature Connect this sensor to DS 60P and compare the reading with the good sensor If 1 sensor input is selected the upper LCD will display the maximum recor...