5-9
Chapter 5. ADVANCED OPERATION
Display Item
Item Description
Setup Item and Description
Factory
Setting
Remarks
C-36
Operational
differential
pressure
setting (control
optimization)
0: Low differential pressure
(50 ± 50 kPa)
1: Standard differential pressure
(200 ± 100 kPa)
2: High differential pressure
(300+0, -100 kPa)
1
When the setting corresponds to the
actual operating differential pressure,
control can be optimized.
(When "0" is set, the control response
speed becomes fast.
When "2" is set, the control response
speed becomes slow.)
*5
C-3
7
Flow rate display
unit change
function
0: Flow rate is displayed in the
standard flow rate unit.
1: Flow rate is displayed in
[L/min] at all times.
-1: Flow rate is displayed in
[mL/min] at all times.
0
0: When the flow rate range or
gas type is changed, the unit is
automatically changed to the
display unit so that the range after
change becomes the maximum
resolution.
1: A value less than 0.001[L/min] is
not displayed
*6
C-38
PV (instantaneous
flow rate) display
decimal point
position change
function
0: Decimal point position is not
changed
1: Decimal point position is
shifted one digit left
-1: Decimal point position is
shifted one digit right
0
The decimal point position of the SP
display is not changed.
1: When the standard decimal point
position is the 4th digit (0.xxx), the
function is invalid even though this
setting is selected. If the flow rate
exceeds the display range, a dash is
displayed for all digits (----).
-1: When the standard flow rate
display does not have a decimal
point, it is invalid even though this
function is selected.
*1. When "4: flow rate setting method switching" is selected in the external contact inputs
c-
10
to
c-
12
in the function
setup, switching according to external input takes precedence.
*2. According to the settings in
c-05
and
c-06
, the analog input and output ranges are changed as shown in the table
below.
Settings
in
C-06
Settings in function setup
C-05
0
1
2
0
0 to 5 V internal reference input/
0 to 5 V instantaneous flow rate output
0 to 5 V external reference input/
0 to 5 V instantaneous flow rate output
1 to 5 V external reference input/
0 to 5 V instantaneous flow rate output
1
0 to 5 V internal reference input/
1 to 5 V instantaneous flow rate output
0 to 5 V external reference input/
1 to 5 V instantaneous flow rate output
1 to 5 V external reference input/
1 to 5 V instantaneous flow rate output
2
0 to 20 mA external reference input/
0 to 20 mA instantaneous flow rate
output
0 to 20 mA external reference input/
0 to 20 mA instantaneous flow rate
output
4 to 20 mA external reference input/
0 to 20 mA instantaneous flow rate
output
3
0 to 20 mA external reference input/
4 to 20 mA instantaneous flow rate
output
0 to 20 mA external reference input/
4 to 20 mA instantaneous flow rate
output
4 to 20 mA external reference input/
4 to 20 mA instantaneous flow rate
output
4
0 to 5 V internal reference input/
0 to 5 V setting flow rate output
0 to 5 V external reference input/
0 to 5 V setting flow rate output
1 to 5 V external reference input/
0 to 5 V setting flow rate output
5
0 to 5 V internal reference input/
1 to 5 V setting flow rate output
0 to 5 V external reference input/
1 to 5 V setting flow rate output
1 to 5 V external reference input/
1 to 5 V setting flow rate output
6
0 to 20 mA external reference input/
0 to 20 mA setting flow rate output
0 to 20 mA external reference input/
0 to 20 mA setting flow rate output
4 to 20 mA external reference input/
0 to 20 mA setting flow rate output
7
0 to 20 mA external reference input/
4 to 20 mA setting flow rate output
0 to 20 mA external reference input/
4 to 20 mA setting flow rate output
4 to 20 mA external reference input/
4 to 20 mA setting flow rate output