5-56
5-6-15. Setting contact output status
This function is used to set contact output status for normal operation.
This function is effective only when contact output has been selected is the function
specification.
Set range: CLOSE Sets the open collector output to ON.
OPEN Sets the open collector output to OFF.
Default: OPEN
Set the contact output status in accordance with the following procedure:
Step
Procedure
Screen
1
Enter ENGINEERING MODE in accordance with the
entry into ENGINEERING MODE (see section 5-5-
10. on page 5-33). Then press the
or
key to
display the screen at right.
12.3 %
# ST. OUT MODE
NORMAL CLOSE
2
Press the
key.
12.3 %
# ST. OUT MODE
NORMAL CLOSE
3
Using the
key, set the contact output status.
12.3 %
# ST. OUT MODE
NORMAL OPEN
4
Press the
key to move the cursor to the position
under #.
Press the MODE key to return to the
MEASUREMENT MODE and to save data.
12.3 %
# ST. OUT MODE
NORMAL OPEN
CAUTION
You have only ten minutes to return to MEASURING MODE to save the new value before
the system resets it to the previously saved value.