![Azbil MagneW Two-wire PLUS+ MTG15A Скачать руководство пользователя страница 102](http://html1.mh-extra.com/html/azbil/magnew-two-wire-plus-mtg15a/magnew-two-wire-plus-mtg15a_user-manual_3042668102.webp)
5-32
5-5-9. Selecting a communication system
Select the communication system (SFC, DE, HART, and communication disable).
Select a communication system to be used. Note that the converter will be rebooted when the
MODE key is pressed to switch to the MEASURING MODE after the settings are changed.
HART: HART communication by using the HART Communicator.
SFN.A: SFC in the analog (4-20 mA) output mode.
SFN.D: DE (Digital Enhanced) communication.
NONE: Communication is not used/disable.
By default, SFN.A: SFC communication is set.
Select a communication system in accordance with the following procedure:
Step
Procedure
Screen
1
The screen at right is a screen display example in
MEASURING MODE (measurement state).
Press the MODE key.
20.0 %
01.94 m
3
/h
WP0
00069401
2
The OPERATOR'S MODE screen appears for approx.
two seconds, and then the damping setting screen
appears.
20.0 %
* OPERATOR'S
MODE
20.0 %
* DAMPING
005.0 s
3
Press the
three times to display the screen as shown
on the right.
20.0 %
* COM SELECT
SFN. A
4
Press the
key to move the cursor to the position for
the communication system (SFN.A, SFN.D, NONE,
HART). The screen at right shows an example where
SFN.A has been selected for the communication
system.
20.0 %
* COM SELECT
SFN. A
5
Press the
or
key to select a desired
communication system to be set.
The screen at right shows an example where HART
communication has been selected.
20.0 %
* COM SELECT
HART
6
Press the
key to move the cursor to the position
under *.
Pressing the MODE key reboots the converter, returns
to MEASURING MODE, and the communication
system changes and saved.
20.0 %
* COM SELECT
HART
8.8.8.8.8.8.8.8
RATE
TOTAL
%
SELF CHECK
MODE
20.0 %
01.94 m
3
/h
WP0
00069401
CAUTION
You have only ten minutes to return to MEASURING MODE to save the new value before
the system resets it to the previously saved value.
Содержание MagneW Two-wire PLUS+ MTG15A
Страница 8: ...vi...
Страница 22: ...1 14...
Страница 56: ...2 34...
Страница 60: ...3 4 Fig 3 2...
Страница 66: ...3 10...
Страница 70: ...4 4...
Страница 144: ...5 74...
Страница 226: ...6 82...
Страница 268: ...7 42...
Страница 274: ...8 6...
Страница 275: ......
Страница 278: ......
Страница 280: ......