1-6
Chapter 1. ETHERCAT COMMUNICATION
■
LED indicators
LED indicators for EtherCAT are explained below.
●
Link/Activity LED: Green
Indicates the status of physical link and data communication at the EtherCAT com-
munication port.
Link/
Activity LED
LED state
Description
Off
Link is not established.
On
Link is established but no data is being communicated.
Blinking
Link is established and data is being communicated.
●
EtherCAT RUN/ERROR LEDs
The RUN LED indicates the status of EtherCAT communication. The ERROR LED
indicates EtherCAT errors.
RUN LED: Green
LED state
Description
Remarks
Off
Init state
No communication is available.
Blinking
The device is in the Pre-
Operational state.
Only mailbox communication is
available.
Single flash
The device is in the Safe-
Operational state.
Process (input) data communication
and mailbox communication are
available.
On
The device is in the Operational
state.
Process (input and output) data
communication and mailbox com-
munication are available.
ERROR LED: Red
LED state
Description
Remarks
Off
No error
There is no EtherCAT error, or the
device is not communicating.
Blinking
EtherCAT communication setting
error
Invalid configuration for EtherCAT
communication
Single flash
Device operation error
There is an application error in this
device.
Double flash
Process data watchdog time-out
EtherCAT watchdog time-out
Sync Manager Watchdog timeout or
EtherCAT communication timeout
has occurred.
On
PDI watchdog time-out
There is a critical error in communi-
cation or application.
LED state
Definition
Blinking
200 ms ON, 200 ms OFF
Single flash
200 ms ON, 1000 ms OFF
Double flash
200 ms ON, 200 ms OFF, 200 ms ON, 1000 ms OFF