Installation
Azbil Corporation
2-10
Model JTD720A - Smart Multivariable Transmitter
Orifice
Differential pressure
output port
Seal pot
Seal pot
Stop valve
Tee
3-way manifold valve
Drain plug
Drain
valve
Drain
valve
Low
pressure side
High
pressure side
High
pressure
side
Low
pressure
side
Stop valve
Differential pressure
output port
Orifice
Figure 2-9
Piping for steam flow measurement
For vertical piping, installing the seal pots at stepped positions as shown in the figure
can prevent zero drift of the differential pressure gauge, which otherwise is apt to
occur. Note that, with stepped seal pots, it is not possible to adjust the zero point in
the usual way using a 3-way manifold valve. Use model CFS100 to adjust a zero
point that shifted when seal pots at stepped positions were filled with water.
Содержание JTD720A
Страница 1: ...CM2 DST720 2001 Smart Multivariable Transmitter Model JTD720A User s Manual...
Страница 34: ...Installation Azbil Corporation 2 16 Model JTD720A Smart Multivariable Transmitter...
Страница 49: ...Azbil Corporation Starting and Stopping this Device Model JTD720A Smart Multivariable Transmitter 3 15...
Страница 50: ...Starting and Stopping this Device Azbil Corporation 3 16 Model JTD720A Smart Multivariable Transmitter...
Страница 70: ...Azbil Corporation 4 20 Model JTD720A Smart Multivariable Transmitter...
Страница 71: ......
Страница 74: ......
Страница 76: ......