Chapter 8. PROGRAM SETUP
●
●
Display
“- - - -” is displayed for the SP and time setting values in non-set
segments.
■
Setting up events 1 to 3 items
●
●
When event type is PV type event
(1) In the setting display state, move to the event 1 to 3 items of the
segment to be set up on the programming map.
(2) If you press
ENT
, the upper display starts blinking to indicate
start of entry to the No.1 setup.
(3) Press
,
,
or
to set to the No.1 setup event
operating point setting.
Setting range: -1999 to +9999 U
0 to 9999 U (in case of absolute value deviation
event)
-10.0 to +110.0% (in case of MV, MFB event)
(4) When you press
ENT
, blinking on the upper display stops.
(When
FUNC
+
CLR
are pressed, the upper display returns to
“- - - -” and stops blinking.)
●
●
Display (PV type event)
• “- - - -” is displayed for the setting values in non-set segments.
• When setup data
C
6
8
is set to 1, event 1 to 3 items on the pro-
gramming map are skipped and not displayed.
SP
TM
SP1 setting value
Time setting value
Program No. Segment No.
Pattern
tendency
EV1 to EV3 and T1 to T5 all out
Operating point setting value
Program No. Segment No.
Pattern
tendency
LEDs corresponding to EV1 to EV3 lit. T1 to T5 all out