Chapter 5 Wiring
5-3. Connecting the power supply and signal cables
CAUTION
Switch off power supply before installing or connecting the transmitter. Failure to
observe this may result in destruction of parts of the electronics.
Cable specification
•
A normal device cable suffices if only the analog signal is used.
•
A shielded cable is recommended for HART
®
communication. Observe grounding
concept of the plant.
Please also observe the general procedure on the page 10.
1
2-
1+
2
3
4
Figure 5-2. Connecting the signal cables and power supply
1. Terminals for HART
®
protocol and power supply
2. Internal ground connection
3. External ground connection
4. Shielded signal cable (recommended for HART
®
protocol)
•
The terminals for connecting the signal cable (1+ and 2−) are protected against reverse
polarity.
•
Conductor cross-section:
•
Max. 2.5 mm
2
for screw terminals
•
Max. 1.5 mm
2
for spring terminals. Min. stripping length of wire10 mm (0.39 in).