5
Install the unit by screwing three screws. It’s recommended to use M4 or M5 screws.
Battery Connection
CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC over-current
protector or disconnect device between battery and inverter. It may not be required to have a disconnect
device in some applications, however, it’s still required to have over-current protection installed. Please refer to
typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use
appropriate cable for battery connection. To reduce risk of injury, please use the
proper recommended cable and terminal size as below.
Recommended battery cable and terminal size:
Model
Typical
Amperage
Battery
Capacity
Wire Size
Ring Terminal
Torque
Value
Cable
mm
2
Dimensions
D (mm) L (mm)
5KW
135A
200AH
2*4AWG
44
6.4
49.7
2~3 Nm
Please follow below steps to implement battery connection:
1.
Assemble battery ring terminal based on recommended battery cable and terminal size.
2.
Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the nuts are
tightened with torque of 2-3 Nm. Make sure polarity at both the battery and the inverter/charge is correctly
connected and ring terminals are tightly screwed to the battery terminals.
Ring terminal: