UMDIO128CO V2.0.1 Preliminary Documentation – May be Subject to Change 20-53
The module will send the following response (any other response is a failure):
Item Value
COB-ID 0x7E4
Length 3
Data 0
0x17
(cs=23 for store configuration)
Data 1
0x00
Data 2
0x00
Set the module state to LSS-operation by
sending
the following message:
(Note, the module will reset itself back to the pre-operational state)
Item Value
COB-ID 0x7E5
Length 2
Data 0
0x04
(cs=4 for switch state global)
Data 1
0x00
(switches to waiting state)
The following screen capture (left) shows the CAN data was sent (7E5h) and received (7E4h) by
the tool when the baudrate was changed to 250 kbps using the LSS protocol. The other image
(right) shows what was printed on an example debug RS-232 menu while the operation took place.
Between CAN Frame 4 and 5, the baudrate on the CAN Scope tool was changed from 125 to 250
kbps.