UMDIO128CO V2.0.1 Preliminary Documentation – May be Subject to Change 16-53
CAN NETWORK CONSTRUCTION
Axiomatic recommends that multi-drop networks be constructed using a “daisy chain” or
“backbone” configuration with short drop lines.
CAN TERMINATION
It is necessary to terminate the network; therefore an external CAN termination is required. No
more than two network terminators should be used on any one single network. A terminator is a
121
Ω
, 0.25 W, 1% metal film resistor placed between CAN_H and CAN_L terminals at the end two
nodes on a network.