UMAX140900RST. Ethernet to CAN Converter. Version 1
Page: 24-41
Set
Auto Connect to Remote
to
No
to disable the client side of the converter. The
Remote IP
Address
and
Remote Port
can be left untouched since they are not used by the converter
when the client mode is disabled. They are grayed on the
Settings
page in this mode.
For the CAN network, configure the necessary
Baud Rate
and set
Loopback Messages
to
No
.
The
Loopback Messages
configuration parameter must be set to
No
to avoid sending the
same messages back and forth between converters, which will lead to network saturation and
communication failure.
An example of the converter configuration as a server is presented in Figure 23.