Set Jumper Configuration:

The unit is sent out with the jumpers set to Gray Code, 1 
floor below reference, and 1 Offset. If these settings do not 
match the installation, change jumpers as follows before 
fitting:

 

+

Remove cable end plate and carefully extract PCB.

 

+

Set jumpers to desired positions. For the offset of 1 floor 
(J7), leave jumper on a single pin.

 

+

Insert board back into channel. Use guides just below 
the centre, and check the direction arrow on the PCB is 
the same as the direction of the arrow on the extrusion 
label.

 

+

Screw end plate back on. Do not trap wires between 
extrusion and end plate.

 

+

Screw mounting bracket on to end plate.

Elevator Position System 

(EPS)

Installation Guide

Full Jumper Functions: 

The jumpers are used to change the function of the sensor, and can be set as follows:

The jumper

Jumper

Label

Function In

Function Out

J10

Seq

Sequential counting.  Each wire on the 
output represents a floor (max 5 floors)

J9

Gray

Gray Code counting

J8

Bin

Binary Code counting

J7

0/1

Floor offset at lowest floor, in Binary and 
Gray modes. 1 if fitted

0 if not fitted

J6

Not used

J5

0

Number of floors below reference floor

J4

-1

J3

-2

J2

-3

J1

-4

 

Note: Jumpers J1 to J5 are set to indicate the number of floors below the reference, so that at the lowest floor the code output 
in Binary or Gray is 00000 (or 00001 if offset set to 1). If more than 1 jumper is fitted for the mode, Binary has precedence, 
followed by Gray code.