Appendix D 

Procedure to Check Transducer Operation 

 

This procedure should only be used for trouble shooting 

 

This procedure requires a 4-20mA current generator.

 

 

1.  Mount the positioner and connect the pneumatics as described in section 3 of this manual. 
2.  Remove the cable that connects the inner canister to the pneumatic transducer assembly. 

The electronic canister does not need to be removed. 

3.  Locate Pin 2 & Pin 4 on transducer pin connector (see figure below). 

a. 

Ref.:

 Pin 1 is furthest from the pressure gages, Pin 10 is nearest to the to the 

pressure gages. 

4.  Connect positive lead of the current generator to Pin 2 and negative lead to Pin 4. 

a. 

Note: 

make sure power on the current generator is turned off before connecting it 

to the pins. Make sure the two leads are not shorting by both coming in contact 
with Pin 3. 

5.  Turn the 4-20 mA generator on. 

a. 

Note: 

the transducer operates between 0 and 3.3 mA. Therefore, make sure when 

turning on the current generator the current is turned down within this range. 
Applying a current greater than 3.3 mA can permanently damage the transducer. 

6.  Apply enough air supply to the positioner. 
7.  The transducer consists of a spool that will channel air between the two output ports of 

the positioner. As the current is raised air is removed from Output Port 2 and applied to 
Output Port 1 of the positioner. 

8.  To check the operation of the positioner, raise and lower the current between 0 and 4 mA. 

This should allow you to fully open and fully close the actuator. You should also be able 
to control the position of the actuator by slowly adjusting the current supply at an 
intermediary (idle) current somewhere between 0 and 3.3 mA. 
 

To Pin 2
(Red+)

To Pin 4
(Black-)

4-20 mA

Signal

Generator

*(Do Not Exceed

3.3 mA)

 

 

Содержание SMARTCAL

Страница 1: ...Prepared By M Twardowski Date 12 17 12 Drafting Work Order 23135 ECN 13247 Reviewed By C Irwin Date 3 14 18 Approved By T Paolini Date 10 18 18 This IOM contains confidential information and is issue...

Страница 2: ...7663 WWW AVIDCONTROLS COM 12 17 12 TECH 440 D W O 23135 Page 2 of 55 Revision History Revision Sept 3 2014 Initial release October 24 2017 Revision A Crane Co Americas 1 201 794 7650 Europe Middle Eas...

Страница 3: ...Level 21 4 2 Automatic Calibration 22 4 3 Proceed to Exiting Calibration or Perform Advanced Calibration 23 4 4 Exiting Calibration 24 4 5 Configure the Positioners Parameters 24 4 6 Manual Override...

Страница 4: ...Schematic for Wiring of Intrinsically safe SmartCal for ATEX IECEX 47 Appendix H 49 Control Schematic for Wiring of Intrinsically safe SmartCal WD 10836 for US CANADA 49 Appendix I 53 Procedure to Re...

Страница 5: ...oop The instrument senses valve position via a non contact Hall Effect sensor and controls valve position through a current to pressure transducer The SmartCal is available in two versions HART and no...

Страница 6: ...and other algorithms By the integration of multiple components into a singular cost efficient unit microprocessor based intelligence can now be used to implement advanced functions such as early warn...

Страница 7: ...Contact Position Feedback To provide consistently accurate performance information all linkages levers and connecting rods from the positioner to the control valve have been eliminated from the design...

Страница 8: ...peration If an error or failure condition occurs it will be displayed on the local LCD or if the positioner is supplied with a HART interface the error codes will be displayed on a hand held terminal...

Страница 9: ...2 TECH 440 D W O 23135 Page 9 of 55 2 Ordering The SmartCal positioner is designed to handle a wide range of control valve applications Please use the following ordering guide to help choose the Smart...

Страница 10: ...LS COM 12 17 12 TECH 440 D W O 23135 Page 10 of 55 3 Initial Setup 3 1 Mounting Positioner on a Rotary Actuator Step 1 Figure 1 shows typical direct mounting of positioner to an actuator Mount the mod...

Страница 11: ...cator to mount as shown in Condition 1 or Condition 2 see figure 3 2 Condition 1 and Condition 2 show the placement of the indicator with respect to the positioner housing while the actuator is in the...

Страница 12: ...eds to be properly oriented Use the symbols on the bottom of the indicator to mount as shown in Condition 1 or Condition 2 see figure 3 3 Condition 1 and Condition 2 show the placement of the indicato...

Страница 13: ...p 5 Remove the electronic canister cover by unscrewing 2 mounting screws Appendix B Procedure to Remove Electronics Cover and Electronic Canister Step 6 If necessary cut remote cable to required lengt...

Страница 14: ...r Step 3 Mount the positioner to the mounting bracket The positioner should be mounted so the magnetic pick up unit of the positioner is centered between the limits of the magnetic assembly s stroke A...

Страница 15: ...he red arrow on the magnet assembly 2 Stroke the actuator to its lower limit and place a mark on the actuator s yoke that lines up with the red arrow on the magnet assembly 3 Place a third mark on the...

Страница 16: ...nsor housing so that the conduit entry faces away from the diaphragm or cylinder See Figure 3 7 Figure 3 7 Note For Fisher actuators model 657 667 sizes 34 thru 70 a slotted mounting kit design can be...

Страница 17: ...nic canister cover by unscrewing 2 mounting screws Appendix B Procedure to Remove Electronics Cover and Electronic Canister Step 5 If necessary cut remote cable to required length making sure to cut e...

Страница 18: ...uator away from the fail position increasing set point signal causes pressure to increase in Outlet Port 1 of the positioner and pressure to decrease in Outlet Port 2 of the positioner Note Air supply...

Страница 19: ...C and above 60 C use field wiring suitable for both minimum and maximum ambient temperatures E Electromagnetic compatibility emissions and susceptibility is guaranteed only if the unit and all cables...

Страница 20: ...CRANE CO 280 N MIDLAND AVE STE 258 SADDLE BROOK NJ 07663 WWW AVIDCONTROLS COM 12 17 12 TECH 440 D W O 23135 Page 20 of 55 Figure3 10...

Страница 21: ...anytime during calibration 4 1 Enter Calibration Menu Level Enter the calibration menu by pushing the CAL button ACAL Auto Cal Menu is the first of four menus By pressing the CAL button again you ente...

Страница 22: ...0 65 liters to a maximum of 600 inch3 9 80 liters for proper Auto Calibration functionality It should also be noted that this is to be used as a general guideline only The actuator valve package dyna...

Страница 23: ...ete The Automatic Calibration that was performed in Section 3 is adequate for most applications If no advanced calibration is required proceed to Section 5 to exit calibration If the user requires usi...

Страница 24: ...L Lo etc press the up arrow key once to enter the Menu level and once more to exit CAL mode If the positioner is performing any calibration function e g ACAL Trnd press up and down key simultaneously...

Страница 25: ...7 Description of Menus The calibration functions of the positioner are organized into the following four menus Menus Menu 1 ACAL Automatic Calibration Menu 2 MCAL Manual Calibration Menu 3 Cofg Confi...

Страница 26: ...tings Menu 4 Stro Manual Override of Input Signal Entering this menu allows you access to the following three stroking functions via the keypad 1 Adjs Adjustment of Positioner to Any Position Using K...

Страница 27: ...CAL and Integral ICAL gain settings can be varied incrementally on a scale from 1 255 The fine tuning values are directly related to the actual time constant values Ti or Td and the Proportional gain...

Страница 28: ...output typically 4 0 mA for zero and 20 0 mA for span The positioner then calculates the difference between the present and the desired output currents for zero and span and uses the differential to a...

Страница 29: ...es LCD menu timeout The range is 1 to 60 minutes It measures the amount of time there is no activity on the keypad and returns the system to the main screen after the configured timeout The default va...

Страница 30: ...ON I 20 5 ON ON ON 5 1 2 Electrical Connection Check the polarity of the 4 20 mA loop current loop The SmartCal terminal strip visually designates the positive and negative terminal points for connect...

Страница 31: ...tCal positioner must be used If the supply pressure is below 40 PSI a low pressure SmartCal positioner must be used See Ordering Guide Section 2 1 5 2 FAQ s Listed here are some FAQ s encountered with...

Страница 32: ...5 2 4 After removing power to the positioner there is full pressure to output port 1 and zero pressure to output port 2 On loss of power the positioner fails full air pressure to output port 2 If thi...

Страница 33: ...itch Maximum voltage 35VDC Maximum load impedance 1 KOhm Performance Resolution 0 2 Full Travel Linearity 0 5 Full Scale Rotary 1 0 Full Scale Linear Hysteresis 0 2 Full Scale Repeatability 0 2 Full S...

Страница 34: ...fully perform calibration ALR Alert 3 Valve position is not being maintained within the dead band range The dead band range EDb is set from the configuration menu during calibration Section 4 The EDb...

Страница 35: ...n Check Hall sensor connector and cable especially if remote see Figure 3 4 connector J8 Pressure supply stability Actuator and tubing leaks Perform a full auto CAL Remove power for at least 1 minute...

Страница 36: ...nd is properly connected to a clean ground reference Sources of electromagnetic noise too close to the sensor or to the positioner cables like AC cables for motors inverters etc Try to replace the Hal...

Страница 37: ...connected Actuator Valve assembly integrity Try to repeat a full auto CAL Call factory for additional support Not possible to set down gain The calibration of the position sensor could not find a pro...

Страница 38: ...or and cable especially if remote see Figure 3 4 connector J8 Magnet assembly For rotary magnets check if it is not rotated 90 degrees see figures 3 2 3 3 and 3 4 For linear magnets check if the magne...

Страница 39: ...additional support Service not implemented An unknown service was request via HART communication Check Remove power for at least 1 minute and retry Remove power for at least 1 minute perform a factory...

Страница 40: ...t the setting of the Error 3 threshold message to indicate low input pressure there is an adjustment screw located on the top of the pneumatic transducer see figure below 3 To set the Error 3 threshol...

Страница 41: ...om electronics canister make sure to note connector locations Remove the screw that secures canister housing and ground cable Remove the screw that secures ground cable see figures below 3 Remove the...

Страница 42: ...utput current to go to a fail state is whenever the onboard microcontroller gets reset by the internal or external watchdog circuits A third event that causes the transmitter output to go to the fail...

Страница 43: ...ore connecting it to the pins Make sure the two leads are not shorting by both coming in contact with Pin 3 5 Turn the 4 20 mA generator on a Note the transducer operates between 0 and 3 3 mA Therefor...

Страница 44: ...ent just prior to the positioner is therefore recommended Spool valve cleaning In favorable conditions i e high quality supply air healthy actuator there will be minimal if any maintenance necessary o...

Страница 45: ...amage the spool assembly and will affect the fit and action of the spool sleeve assembly Important the spool and sleeve assembly are sold as a precision matched set Spools are not interchangeable To p...

Страница 46: ...CRANE CO 280 N MIDLAND AVE STE 258 SADDLE BROOK NJ 07663 WWW AVIDCONTROLS COM 12 17 12 TECH 440 D W O 23135 Page 46 of 55 Appendix F Grounding Schematic...

Страница 47: ...d apparatus C Ci of SmartCal cable capacitance Ca of associated apparatus 2 Associated apparatus manufacturer s installation drawing must be followed when installing this equipment 3 Control equipment...

Страница 48: ...h combined entity parameters The following conditions must be satisfied Voc or Vo Vmax or Ui Ca Ci Ccable Isc or Io Imax or Ii La Li Lcable 2 Associated apparatus manufacturer s installation drawing m...

Страница 49: ...ed apparatus and the SmartCal cable inductance should be determined in accordance with ROSEMOUNT installation drawing 00475 0081 2 Associated apparatus manufacturer s installation drawing must be foll...

Страница 50: ...fety each field wiring pair 4 20 mA and Analog Output must be run in separate cables or separate shields connected to intrinsically safe Associated Apparatus ground 4 ROSEMOUNT 475 HART COMMUNICATOR i...

Страница 51: ...fety each field wiring pair 4 20 mA and Analog Output must be run in separate cables or separate shields connected to intrinsically safe Associated Apparatus ground 4 ROSEMOUNT 475 HART COMMUNICATOR i...

Страница 52: ...Ci C Cable Isc or Io Imax or Ii La Li L Cable 2 Associated apparatus manufacturer s installation drawing must be followed when installing this equipment 3 Control equipment connected to associated ap...

Страница 53: ...row to select Yes or press once more to select All Then press the CAL button to begin the factory default procedure a Yes option resets all non volatile data to default with exception of the position...

Страница 54: ...CRANE CO 280 N MIDLAND AVE STE 258 SADDLE BROOK NJ 07663 WWW AVIDCONTROLS COM 12 17 12 TECH 440 D W O 23135 Page 54 of 55 Appendix J HART Communicator Menu Flow Chart SmartCal Digital Valve Controller...

Страница 55: ...s control systems and asset management systems in the market Crane Co provides DD files and DTM for this integration DD files can be downloaded from http www hartcommproduct com inventory2 index php a...

Отзывы: