TONE-BD (Tone-Clock Circuit)
Issue 1 May 2002
8-1673
555-233-143
c. Error Type 23
The circuit pack has been logically administered but not
physically installed. Installing the circuit pack will resolve the alarm.
d. Error Type 125
A wrong circuit pack is inserted in the slot where this
circuit pack is logically administered. To resolve this problem, either:
1. Remove the wrong circuit pack, and insert the logically administered
circuit pack.
or
Use the change circuit-pack command to re-administer this slot to
match the circuit pack inserted.
e. Error Type 126
The port network specified in the
PORT
field of the error
log entry booted up without a Tone-Clock circuit pack, or with a one that
cannot communicate at all with the system. The error is logged five
minutes after the port network is restarted. If no circuit pack is present,
install one of the proper code. If there is a circuit pack present, replace it.
See
‘‘Replacing the IPSI or Tone-Clock Circuit Pack’’
f. Error Type 257
Τ
his error indicates transient communication problems
with this circuit pack. This error is not service-affecting and no action is
required.
g. Error Type 513
This circuit pack has an on-board hardware failure.
Replace the circuit pack using the procedure described in
IPSI or Tone-Clock Circuit Pack’’
h. Error Type 76 — This error can be ignored, but look for other errors on this
circuit pack.
i. Error Type 1025 — This error is not service-affecting and no action is
required.
j. Error Type 1538 — The circuit pack was taken out of service because of
an excessive rate of uplink messages. Use test tone-clock PC long to
reset the circuit pack and put it back into service. If the command is not
successful, replace the circuit pack using the procedure described in
‘‘Replacing the IPSI or Tone-Clock Circuit Pack’’
. If the alarmed circuit
pack is the active Tone-Clock of a duplicated pair, first interchange
Tone-Clocks via the set tone-clock PC command to avoid a service
outage. If the error occurs again within 15 minutes, follow normal
escalation procedures.
k. Error Type 2049 or 2305
These errors indicate the loss of one or more
clock signals from the reported IPSI or Tone-Clock circuit pack, which was
active at the time of the error. The effect of any of these errors is described
in the table for error type 1. Diagnosis of the problem is the same for all
four error types, with the exception noted below.
1. Examine the Hardware Error Log for errors reported against circuit
packs in the same port network, especially TDM-CLK, TONE-BD,
and EXP-INTF. Follow the repair or replacement procedures
indicated for any such errors found.
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...