POWER
Issue 1 May 2002
8-1311
555-233-143
Battery and Charger for DC-Powered Systems
NOTE:
This MO applies to the J58890CE and the J58890CH-1 with large battery
holdover.
This MO represents the battery backup unit found in AC-powered multicarrier
cabinets. Because the system does not recognize the type of external power, this
MO exists in DC-powered multicarrier cabinets but serves no functional purpose.
In such cabinets, every POWER test should always either pass or abort, and no
POWER alarms should be raised.
S8700 Multi-Connect systems support two different types of PN cabinets:
multicarrier and single-carrier. Both cabinet types may be powered by either AC
or DC external power source. Environmental maintenance differs according to
cabinet type and external power supply.
Error Log Entries and Test to Clear Values
Note:
a. This error occurs is valid only for AC-powered multicarrier cabinets with
battery backup. For DC-powered cabinets, you cannot clear the error and
it should be ignored.
MO’s Name (in
Alarm Log)
Alarm
Level
Initial SAT Command
to Run
1
1.
UU is the cabinet number indicated in the PORT field from the Alarm or Error Log.
Full Name of MO
POWER
MINOR
test environment UU
Battery and Battery Charger
Table 8-525.
Battery and Battery Charger Error Log Entries
Error
Type
Aux
Data
Associated Test
Alarm
Level
On/Off
Board
Test to Clear Value
0
1
1.
Run the short test sequence first. If every test passes, run the long test sequence. Refer to each appropriate
test’s description, and follow its recommended procedures.
0
Any
Any
Any
test environment UU sh r 1
1
Any
Battery and Battery Charger
Query test (#5) (error code 8)
MINOR
ON
test environment UU s r 1
257
Any
Battery and Battery Charge
Query test (#5) (error code 4)
MINOR
ON
test environment UU s r 1
769
Any
Battery and Battery Charger
Query test (#5) (error code 2)
MINOR
ON
test environment UU s r 1
3840 (a)
1005,
1028
Associated Battery and Battery
Charger Query test (#5)
test environment UU s r 1
Содержание S8700 Series
Страница 50: ...Maintenance Architecture 555 233 143 1 26 Issue 1 May 2002 ...
Страница 74: ...Initialization and Recovery 555 233 143 3 12 Issue 1 May 2002 ...
Страница 186: ...Alarms Errors and Troubleshooting 555 233 143 4 112 Issue 1 May 2002 ...
Страница 232: ...Additional Maintenance Procedures 555 233 143 5 46 Issue 1 May 2002 ...
Страница 635: ...status psa Issue 1 May 2002 7 379 555 233 143 status psa See status tti on page 7 406 ...
Страница 722: ...Maintenance Commands 555 233 143 7 466 Issue 1 May 2002 ...
Страница 1121: ...CARR POW Carrier Power Supply Issue 1 May 2002 8 399 555 233 143 Figure 8 19 Power Distribution Unit J58890CH 1 ...
Страница 1447: ...E DIG RES TN800 reserve slot Issue 1 May 2002 8 725 555 233 143 E DIG RES TN800 reserve slot See ASAI RES ...
Страница 1735: ...LGATE AJ Issue 1 May 2002 8 1013 555 233 143 LGATE AJ See BRI SET LGATE BD See BRI BD LGATE PT See BRI PT ...
Страница 1846: ...Maintenance Object Repair Procedures 555 233 143 8 1124 Issue 1 May 2002 Figure 8 62 TN787 MMI MULTIMEDIA INTERFACE CIRCUIT PACK ...