H323-SGRP (H.323 Signaling Group)
Issue 4 May 2002
10-875
555-233-123
Table 10-315.
TEST #1386 CLAN Ethernet Status Test
Error
Code
Test
Result
Description/Recommendation
1125
ABORT
Ethernet Link is not in service.
1. Check if the ethernet link is in-service or not. If the link
is not in service, release the link using release link n
or the release port UUCSSpp command and repeat
the test. This is a normal abort.
2. If the test continues to abort after following the repair
procedures, escalate the problem.
2000
ABORT
Response to the test was not received from the CLAN TN799
circuit pack within the allowable time period.
1. If this result occurs repeatedly, attempt to reset the
circuit pack if the other ports on the board are not in
use (Yellow LED is off). Reset the circuit pack by
issuing the busyout board UUCSS, reset board
UUCSS, and release board UUCSS commands.
2. If this result occurs again, replace the circuit pack.
2100
ABORT
The necessary system resources to execute the test could not
be allocated.
1. Retry the command at 1-minute intervals a maximum
of 5 times.
2500
ABORT
Internal system error.
1. Retry the command at 1-minute intervals a maximum
of 3 times
FAIL
The CLAN ethernet port corresponding to the near-end address
of the SIG-GRP that is OOS has failed. All sessions are down.
1. Execute test port UUCSSpp long and verify the
result of the H.323 Signaling Group Ping Test (#1387).
If the test continues to fail, escalate the problem. If the
test passes wait for the sessions to come up.
PASS
The CLAN ethernet port corresponding to the near-end address
of the SIG-GRP that is in-service has passed this test. All
sessions on the ethernet link are up.
Continued on next page
Содержание Definity SI
Страница 1: ...0DLQWHQDQFH IRU YD D 1 7 6HUYHU 6 Volumes 1 2 and 3 555 233 123 Issue 4 May 2002...
Страница 62: ...Maintenance Architecture 555 233 123 1 26 Issue 4 May 2002...
Страница 92: ...Management Terminals 555 233 123 3 26 Issue 4 May 2002...
Страница 204: ...Routine Maintenance Procedures 555 233 123 5 100 Issue 4 May 2002...
Страница 250: ...LED Interpretation 555 233 123 7 10 Issue 4 May 2002...
Страница 2763: ...VC DSPPT Issue 4 May 2002 10 1977 555 233 123 Figure 10 107 VC Circuit Pack DSP Port Local TDM Loopback Test...
Страница 2776: ...Maintenance Object Repair Procedures 555 233 123 10 1990 Issue 4 May 2002 Figure 10 109 VC Circuit Pack Summer Port Loopback Test...
Страница 2804: ...Maintenance Object Repair Procedures 555 233 123 10 2018 Issue 4 May 2002...
Страница 2968: ...Index 555 233 123 IN 10 Issue 4 May 2002...