Autonics TX4S Series Скачать руководство пользователя страница 1

 

1:  When using the unit at low temperature (below 0

℃), display cycle is slow. 

 Control output operates normally. 

 

2:   At room temperature(23

±5

)

             TC R(PR), S(PR) , below 200

: (PV ±0.5% or ±3

, select the higher one) ±1 digit

, over 200

: (PV ±0.5% or ±2

, select the higher one) ±1 digit

             TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±2

, select the higher one) ±1 digit

         Out of room temperature range

             TC R(PR), S(PR): (PV ±1.0% or ±5

, select the higher one) ±1 digit                                  

             TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±3

, select the higher one) ±1 digit

3: The weight includes packaging. The weight in parentheses is for unit only. 

Environment resistance is rated at no freezing or condensation. 

 Ordering Information

 Specifications

 Input Type And Range

TX

4 S

1 4 R

Item

Digit

Size

Option output

Power supply

Control output

R

Relay output

S

SSR drive output

C

Selectable current output or SSR drive output 

4

100-240VAC 50/60Hz

1

Alarm output 1

2

Alarm output 1+Alarm output 2

A

Alarm output 1+Alarm output 2+Trans. output

B

Alarm output 1+Alarm output 2+RS485 com. output

S

DIN W48×H48mm

4

9999(4 digit)

TX

LCD display standard PID temperature controller

Series

TX4S

Power supply

100-240VAC 50/60Hz

Allowable voltage range 90 to 110% of rated voltage

Power consumption

Max. 8VA

Display method

11 segments (PV: white, SV: green), other display (yellow) with LCD method

1

Character 

size

PV(W×H)

6.9×15.3mm

SV(W×H)

4.1×9.2mm

Input type RTD

DPt100Ω, Cu50Ω (permissible line resistance max. 5Ω)

TC

K(CA), J(IC), L(IC), T(CC), R(PR), S(PR)

Display 

accuracy

2

RTD

●At room temperature (23

±5

): (PV ±0.3% or ±1

, select the higher one) ±1digit

Out of room temperature: (PV ±0.5% or ±2

, select the higher one) ±1digit

TC

Control 

output

Relay

250VAC 3A 1a

SSR

Max. 12VDC ± 2V 20mA

Current

DC4-20mA or DC0-20mA (load resistance max. 500Ω)

Option 

output

Alarm output AL1, AL2 Relay: 250VAC 3A 1a

Trans. output DC4-20mA (load resistance max. 500Ω, output accuracy: ±0.3%F.S.)

Com. output RS485 Communication output (Modbus RTU method)

Control method

ON/OFF control, P, PI, PD, PID control

Hysteresis

1 to 100

/

℉ 

(0.1 to 50.0

/

) variable

Proportional band(P)

0.1 to 999.9

/

Integral time(I)

0 to 9999 sec.

Derivative time(D)

0 to 9999 sec.

Control period(T)

0.5 to 120.0 sec.

Manual reset

0.0 to 100.0%

Sampling period

50ms

Dielectric strength

3,000VAC 50/60Hz for 1 min. (between all terminals and case)

Vibration

0.75mm amplitude at frequency 5 to 55Hz (for 1 min.)in each X, Y, Z direction for 2 hours

Relay

life cycle

Mechanical OUT, AL1/2: Min. 5,000,000 operations

Electrical

OUT, AL1/2: Min. 200,000 (250VAC 3A resistance load)

Insulation resistance

Min. 100MΩ (at 500VDC megger)

Noise resistance

Square shaped noise by noise simulator (pulse width 1

) ±2kV R-phase, S-phase

Memory retention

Approx. 10 years (non-volatile semiconductor memory type)

Environ-

ment

Ambient temp. -10 to 50

, storage: -20 to 60

Ambient humi. 35 to 85%RH, storage: 35 to 85%RH

Protection structure

IP50 (front panel, IEC standards)

Insulation type

Double insulation (mark: 

: , 

dielectric strength between all terminals and case: 3kV)

Approval

Weight

3

Approx. 135.2g (approx. 85.2g)

 Connection

 Unit Description

Input type

Decimal point Display

Input range(

)

Input range(

)

Thermocouple

K(CA)

1

KCaH

-50 to 1200

-58 to 2192

0.1

KCaL

-50.0 to 999.9

-58.0 to 999.9

J(IC)

1

JIcH

-30 to 800

-22 to 1472

0.1

JIcL

-30.0 to 800.0

-22.0 to 999.9

L(IC)

1

LIcH

-40 to 800

-40 to 1472

0.1

LIcL

-40.0 to 800.0

-40.0 to 999.9

T(CC)

1

TCcH

-50 to 400

-58 to 752

0.1

TCcL

-50.0 to 400.0

-58.0 to 752.0

R(PR)

1

RPR

0 to 1700

32 to 3092

S(PR)

1

SPR

0 to 1700

32 to 3092

RTD

DPt 100Ω 1

DPtH

-100 to 400

-148 to 752

0.1

DPtL

-100.0 to 400.0

-148.0 to 752.0

CU50Ω

1

CUsH

-50 to 200

-58 to 392

0.1

CUsL

`-50.0 to 200.0

-58.0 to 392.0

Mount the unit on the panel. Push the bracket with 

tools to fix the unit as the figure. 

 Installation

1. Measured value (PV) component:

 

RUN mode: Displays current measured value (PV). 

SETTING mode: Displays parameters.

2. Setting value (SV) display component:

 

RUN mode: Displays setting value(SV).

SETTING mode: Displays setting value of parameter.

3. Temperature unit(

/

) indicator:

 

Displays the set temperature unit as temperature unit [

UNIT

] of 

parameter 2 group.

4. Control output (OUT1) indicator:

 Turns ON while control output is ON.

 Turns ON when MV is over 3.0% at cycle/phase control of SSR drive 

output method. 

5. Alarm output (AL1, AL2) indicator:

 

Turns ON when the corresponding alarm output turns ON.

6. Auto-tuning indicator:

 

Flashes during auto-tuning every 1 sec.

● Parameter 2 group

Input sensor

3 sec.

 4 sec.

RUN mode

Setting range: Refer to '

 Input Type And Range'.

Appears only in transmission output model(TX4S-A4 ).

 When changing the 

setting value, 

[

AL1

AL2

parameter of 

parameter 1 group 

is reset.

PAR2

IN-T

KCaH

1

Temp. unit

 When changing the setting value, SV, [

IN-B

H-SV

/

L-SV

AL1

AL2

LBaB

AHYS

] parameters of 

parameter 2 group are reset. 

UNIT

?F

?C

Input 

correction

Setting range:  -999 to 999

/

(-199.9 to 999.9

/

)

IN-B

0

Input digital 

filter

Setting range: 0.1 to 120.0 sec.

MAvF

)1

SV low-limit 

value

Setting range:  Within temperature range of each sensor[

L-SV

≤(

H-SV

-1digit)]

 When changing the setting value, and SV

L-SV

, SV is reset as 

L-SV

.

L-SV

-50

SV high-limit 

value

Setting range:  Within temperature range of each sensor [

H-SV

≥(

L-SV

+1digit)]

 When changing the setting value, and SV

H-SV

, SV is reset as 

H-SV.

H-SV

1200

Control

output mode

O-FT

HEAT

COOL

 Appears only in selectable current output or SSR drive 

output model(TX4S- 4C). 

Control 

output 

selection

OUT

CURR

SSR

SSR drive 

output 

method

 Appears only in SSR drive output model 

(TX4S- 4S). 

SSrM

STND

CYCL

PHAS

Current 

output 

range

 Appears only when control output[

OUT

] is set as 

CURR

.  

oMA

4-20

0-20

Control 

cycle

Setting range: 0.5 to 120.0 sec.

 Appears only when control method[

C-MD

] is 

PID

.

 Does not appear when SSR drive output is set as 

CYCL

, or 

PHAS

T

2)0

Alarm 

output 

hysteresis

Setting range: 1 to 100

/

(0.1 to 100.0

/

)

 Does not appear when AL1/AL2 alarm operation[

AL-1

AL-2

] is set 

as 

AM)_

/

SBa

/

LBa

.

AHYS

1

LBA 

monitoring 

time

Setting range: 0 to 9999 sec.(automatically set during auto-tuning)

 Appears only when alarm operation[

AL-1

AL-2

] is set as 

LBa

.

LBaT

0

Setting range:  0 to 999

/

(0.0 to 999.9

/

)

(automatically set during auto-tuning)

 Appears only when alarm operation [

AL-1

AL-2

] is set as 

LBa

 

and [

LBaT

] is not set as 

0

.

LBA 

detection 

band

LBaB

2

Trans. 

output low-

limit value

Trans. 

output high-

limit value

FS-L

-50

FS-H

1200

Comm. 

address

Setting range: 1 to 127

ADRS

1

Comm. 

speed

Setting range: 24, 48, 96, 192, 384 bps

Multiply 100 to read the setting value.

BPS

96

 

AT

 does not appear when control method [

C-MD

is set as 

ONOF

.

Digital 

input key

DI-K

AlRE

OFF

AT

STOP

Control 

output MV for 

input break

Setting range: 0.0 to 100.0%

 Only 

)0

(OFF)/

10)0

(ON) appear when control method 

[

C-MD

] is set as 

ONOF

.

 When control method [

C-MD

] is changing 

PID

ONOF

 and the setting 

value is below 

10)0

, it is reset as 

)0

ErMV

)0

2

 Setting range: Refer to '

 Input Type And Range'. 

 When changing the setting value, SV, [

IN-B

H-SV

/

L-SV

,

 

AL1

AL2

LBaB

AHYS

] parameters of parameter 2 group are 

reset. 

AL2

operation

AL-2

AM@A

※ 

Set method is same as AL1 alarm 

operation[

AL-1

]. 

 Appears only in alarm output 2 models. 

NONE

EVEN

ODD

Comm. 

parity-bit

PRTY

Setting range: 5 to 99ms

Comm. 

response 

waiting time

RSwT

20

Comm. 

stop-bit

STP

2

1

Comm. 

write

COMW

EnA

DIsA

AL1

operation

 Press the   key to switch 'Alarm operation'   

'Alarm option' setting.

AL-1

Alarm operation

LBaA

AM!A

 Alarm option

AM!A

AM!B

 Appears in RS485 

communication output 

model(TX4S-B4 ). 

Control 

method

C-MD

PID

ONOF

Lock

LOC

LOC1

LOC2

LOC3

OFF

OFF

Unlock

LOC1

Parameter 2 group lock

LOC2

Parameter 1,2 group lock

LOC3

Parameter 1,2 group, SV setting lock

 When changing the setting value, [

ErMV

] is reset as 

)0

[

DI-K

] is reset as 

OFF

.

7.  

 

key:

 Enters parameter group, returns to RUN mode, moves parameters, 

 and saves the setting value. 

8. Setting value adjutment key:

 Enters SV setting mode and move digits. 

9. Digital input key:

  Press the  +  keys for 3 sec. to execute the digital input key 

functions which is set at digital input key[

DI-K

]of parameter 2 group (RUN/STOP, 

clear alarm output, auto-tuning).

10. PC loader port:

 It is for serial communication to set parameter and monitoring by

DAQMaster installed in PC. Use this for connection EXT-US (converter cable, 

sold separately) + SCM-US (USB to Serial converter, sold separately).

AL1 OUT:

250VAC 3A 1a

RESISTIVE LOAD

OUT

SSR

12VDC±2V 20mA Max.

Current

DC0/4-20mA

Load 500ΩMax.

Relay

250VAC 3A 1a

RESISTIVE LOAD

AL2 OUT:

250VAC 3A 1a

RESISTIVE LOAD

SOURCE

100-240VAC

50/60Hz 8VA

mA

1

7

2

8

3

9

4

10

5

11

6

12

18

17

16

15

14

13

RS485(B-)

Communication 

Output 

Transfer Output

DC4-20mA

RS485(A+)

SENSOR

TC

RTD

+

+

-

-

mA

+

-

+

-

B'

B

A

Shaded terminals is standard model.

I N S T R U C T I O N   M A N U A L

Thank you for choosing our Autonics product.

Please read the following safety considerations before use.

 Safety Considerations

Warning

 

Please observe all safety considerations for safe and proper product operation to avoid hazards.

Safety considerations are categorized as follows.

Warning

 Failure to follow these instructions may result in serious injury or death.

Caution 

Failure to follow these instructions may result in personal injury or product damage.

The symbols used on the product and instruction manual represent the following

 symbol represents caution due to special circumstances in which hazards may occur. 

Caution

 The above specifications are subject to change and some models may be discontinued 

without notice.

Setting range: 

1

2
9

3

4

5

6

7

8

10

LCD Display PID Temperature Controller

TX4S SERIES

1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury 

or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, 

railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.) 

Failure to follow this instruction may result in personal injury, fire, or economic loss.

2. The unit must be installed on a device panel before use.

Failure to follow this instruction may result in electric shock.

3. Do not connect, repair, or inspect the unit while connected to a power source.

Failure to follow this instruction may result in electric shock.

4. Check the terminal numbers before connecting the power source.

Failure to follow this instruction may result in fire. 

5. Do not disassemble or modify the unit. Please contact us if necessary.

Failure to follow this instruction may result in electric shock or fire.

1. Do not use the unit outdoors.

Failure to follow this instruction may result in shortening the life cycle of the unit, or electric shock. 

2. When connecting the power input and relay output cables, use AWG20 (0.05mm

2

) cables and make 

sure to tighten the terminal screw bolt above 0.74N.m to 0.90N.m. 

Failure to follow this instruction may result in fire due to contact failure.

3. Use the unit within the rated specifications.

Failure to follow this instruction may result in shortening the life cycle of the unit, or fire. 

4. Do not use loads beyond the rated switching capacity of the relay contact.

Failure to follow this instruction may result in insulation failure, contact melt, contact failure, relay broken, or fire.

5. Do not use water or oil-based detergent when cleaning the unit. Use dry cloth to clean the unit.

Failure to follow this instruction may result in electric shock or fire. 

6.  Do not use the unit where flammable or explosive gas, humidity, direct sunlight, radiant heat, 

vibration, or impact may be present.

Failure to follow this instruction may result in fire or explosion.

7. Keep dust and wire residue from flowing into the unit.

Failure to follow this instruction may result in fire or product damage. 

8. Check the polarity of the measurement input contact before wiring the temperature sensor. 

Failure to follow this instruction may result in fire or explosion.

9.  For installing the unit with reinforced insulation, use the power supply unit which basic level is 

ensured. 

 Dimensions

(unit:mm)

RSA-COVER(48×48mm)

 Bracket

 Terminal cover(sold separately)

5

45

48

44.8

 Panel cut-out dimensions

Min. 65

45

+0.6

   0

45

+0.6    

0

Min. 65

SV setting

Parameter 1 group[

PAR1

]

Parameter 2 group[

PAR2

]

Press any key among 

,  ,  ,   once.

 

 

4 sec.

 

 

2 sec.

 

 

3 sec.

 

 

3 sec.

RUN mode

Setting range:  Deviation alarm(-[F.S] to [F.S]),  

Absolute value alarm(temperature range)

 Does not appear when AL1/AL2 alarm operation[

AL-1

AL-2

of parameter 2 group is set as 

AM)_

/

SBa

/

LBa

.

Only alarm output 2 models have [

AL2

]. 

1:  : Press any key among  ,  ,  .

2: Press the 

 key once after changing the setting value, to save the setting 

value and move to the next parameter

 Hold the 

 key for 3 sec. to save the setting value and return to RUN mode 

after changing the setting value. 

 

 

Dotted parameters may not appear by model type or other parameter 

settings.

Setting range: 0.1 to 999.9

/

Hysteresis

Manual reset

Derivative time

Integral time

Proportional band

Auto-tuning

1

AL2 temperature

AL1 temperature

Setting range: 0 to 9999 sec.

 Integral operation will be OFF

when the setting value is '0.

Setting range: 0 to 9999 sec.

 Derivative operation will be OFF

when the setting value is '0.

Setting range: 0.0 to 100.0%

 Only appears in P, PD control.

Setting range: 1 to 100

/

 (0.1 to 50.0

/

)

 Only appears when control method [

C-MD

] of parameter 2 group is 

set as 

ONOF

.

 When setting as 

ON

, the unit starts auto-tuning. After 

completing, 

OFF

 is automatically set.

 During auto-tuning, the auto-tuning indicator 

flashes (every 1 sec.).

AL1

AT

P

I

PAR1

D

REST

ON

OFF

1)0

0

0

5)0

2

HYS

 

3 sec.

 2 sec.

RUN mode

AL2

2

1250

1250

 Only appears when control 

method [

C-MD

] of parameter 

2 group is set as 

PID

.

● Parameter 1 group

● SV setting  

To change set temperature from 210

 to 250

Order of parameter setup 

Parameter 2 group

Parameter 1 group

SV setting

 

All parameters are related one another. Set the parameters as above order. 

If there is no key input for 30 sec. while setting SV or the parameters, the new settings are ignored, and 

the unit will return to RUN mode with previous settings. 

 When returning to RUN mode by holding the 

 key for over 

3 sec., press the 

 key within 

 1 sec. to 

re-enter the first parameter of previous parameter group. 

Hold the  + +  keys for 5 sec. in RUN mode, to enter re-set parameter menu. Select '

YES

' and all 

parameters are reset as factory default. 

Change SV  

by  ,  ,   key

Press any key among 

,  ,  ,   once.

RUN mode

SV setting mode

③ 

Completes SV 

setting

Check SV

 Parameter Groups

1:  : Press any key among  ,  ,  .

2: Press the 

 key once after changing the setting value, to save the setting 

value and move to the next parameter

 Hold the 

 key for 3 sec. to save the setting value and return to RUN mode 

after changing the setting value. 

 

 

Dotted parameters may not appear by model type or other parameter 

settings.

48.4

9.8

41.5

18

22

22.5

31

55

56

20

15

21

5

45

16

48.6

44.9

36