background image

 

 Caution for your safety

Warning

Please keep these instructions and review them before using this unit.

Please observe the cautions that follow;

Warning

 

Serious injury may result if instructions are not followed.

Caution

  

Product may be damaged, or injury may result if instructions are not followed.

The following is an explanation of the symbols used in the operation manual.

Caution: Injury or danger may occur under special conditions.

Caution

It may cause malfunction if above instructions are not followed.

The above specifications are subject to change without notice.

M       A       N       U       A       L

Thank you very much for selecting Autonics products.

For your safety, please read the following before using.

TEMPERATURE CONTROLLER

TAS/TAM/TAL SERIES

1. In case of using this unit with machinery(Ex: nuclear power control, medical equipment, ship, vehicle, 

train, airplane, combustion apparatus, safety device, crime/disaster prevention equipment, etc) which 

may cause damages to human life or property, it is required to install fail-safe device.

It may cause a fire, human injury or damage to property

2. It must be mounted on Panel.

It may give an electric shock.

3. Do not connect, inspect and repair terminals when it is power on.

It may give an electric shock.

4. Please check the number of terminal when connecting power or input.

It may cause a fire.

5. Do not disassemble or modify this unit, please contact us when it is required. 

It may cause a fire and give an electric shock.

1:

 

<Except normal temperature range> Below 100

 model is F.S. ±4%, Over 100

 model is F.S. ±3%

2: The weight is with packaging and the weight in parentheses is only unit weight.

Environment resistance is rated at no freezing or condensation.

1. Deviation indicator

It shows deviation of present temperature(PV) based on set temperature(SV) by LED.

Input deviation indicator[Deviation indicator:  (green), ▲/▼(red)]

This is the same as Fahrenheit(

).

When power is on, all indicators light for 2 sec., then all indicators turn off and control 

operation starts.

2. Set temperature(SV) dial 

Dial to change set temperature (SV). When changing set temperature, it is applied after 2 sec. for the stable 

input. 

3. Input sensor 

Indicates sensor type of present value. 

Input sensor type or input range each product is shown in the below table. 

Set temperature within input range each sensor.

4. Temperature unit 

Indicates temperature unit(

) of set temperature(SV) and present value(PV).

5. Temperature range 

Indicates temperature range of set temperature(SV) 

6. Control output indicator 

Turns ON when control output (Relay Output/SSR Output) 

7. Control mode selection switch 

Select PID control or ON/OFF control using switch.

8. Terminal block 

Terminals for external connections. For more information, refer to '  Connections'.     

Input Sensor

Range No.

Input range(

)

Input range(

)

Thermocouple

K(CA)

1

0 to 100

32 to 212

2

0 to 200

32 to 392

4

0 to 400

32 to 752

6

0 to 600

32 to 1,112

8

0 to 800

32 to 1,472

C

0 to 1,200

32 to 2,192

J(IC)

2

0 to 200

32 to 392

3

0 to 300

32 to 572

4

0 to 400

32 to 752

RTD

DPt100Ω

0

-50 to 100

-58 to 212

1

0 to 100

32 to 212

2

0 to 200

32 to 392

4

0 to 400

32 to 752

1. Please use separated line from high voltage line or power line in order to avoid inductive noise.  

2. Install power switch or circuit-breaker in order to on/off the power. 

3. The switch or circuit-breaker should be installed nearby users for safety.

4. Do not use this product as Volt-meter or Ampere-meter, this is a temperature controller.

5. In case of using RTD sensor, 3-wire type must be used. If you need to extend the line, 3 wires must be used 

with the same thickness as the line. It might cause the deviation of temperature if the resistance of line is 

different.

6. In case of making power line and input signal line closely, line filter for noise protection should be installed at 

power line and input signal line should be shielded.

7. Keep away from the high frequency instruments. (High frequency welding machine & sewing machine, large 

capacity SCR controller)

8. Installation environment

It shall be used indoor.

Altitude Max. 2,000m 

Pollution Degree 2

Installation Category 

1. This unit shall not be used outdoors.

It might shorten the life cycle of the product or give an electric shock.

2. When wire connection, AWG 20(0.50mm²) should be used and screw bolt on terminal block with 0.74 

to 0.90N·m strength.

It may result in malfunction or fire due to contact failure. 

3. For crimpled terminal, select following shaped terminal.

4. Please observe specification rating.

It might shorten the life cycle of the product and cause a fire.

5. Do not use the load beyond rated switching capacity of Relay contact. 

It may cause insulation failure, contact melt, contact failure, relay broken, fire etc.

6. In cleaning the unit, do not use water or an oil-based detergent.

It might cause an electric shock or fire that will result in damage to the product.

7. Do not use this unit at place where there are flammable or explosive gas, humidity, direct ray of the 

sun, radiant heat, vibration, impact etc.

It may cause a fire or explosion.

8. Do not inflow dust or wire dregs into inside of this unit.

It may cause a fire or mechanical trouble.

9. Please wire properly after checking the polarity of terminals when connect thermocouples.

It may cause a fire or explosion.

10. In order to install the units with reinforced insulation, use the power supply unit which basic 

insulation level is ensured.

 Caution for using

 Major products

Max. 5.8mm

Max. 5.8mm

Series

TAS

TAM

TAL

Power supply

100-240VAC 50/60Hz

Allowable voltage range

90 to 110% of rated voltage

Power consumption

Max. 4VA

Size

DIN W48 x H48mm

DIN W72 x H72mm

DIN W96 x H96mm

Display method

Deviation LED(red, green), Output LED(red)

Setting type

Dial setting

Setting accuracy

F.S. ±2% (room temperature 23

℃ 

±5

)

1

Input

type

RTD

DPt 100Ω(allowable line resistance max. 5Ω per a wire)

Thermocouples

K(CA), J(IC)

Control

ON/OFF Control Hysteresis: 2

 Fixed 

PID Control 

Control period: Relay output 20 sec./SSR drive output 2 sec. 

Control

output

Relay

250VAC 3A 1c 

SSR 

Max. 12VDC±2V 20mA

Functions

PV deviation indication, Error indication

Dielectric strength

2,000VAC 50/60Hz for 1minute(between input terminal and power terminal)

Vibration

0.75mm amplitude at frequency of 5 to 55Hz in each of X, Y, Z directions for 2hours

Relay life 

cycle

Mechanical

Min. 10,000,000 operation(18,000 times/hr)

Electrical

Min. 100,000 operation(900 times/hr)

Insulation resistance

Min. 100MΩ(at 500VDC megger)

Noise strength

Square shaped noise by noise simulator(pulse width 1

) ±2kV R-phase and S-phase

Memory retention

Approx. 10 years (when using non-volatile semiconductor memory type)

Environ

-ment

Ambient temperature -10 to 50

 , Storage: -20 to 60

Ambient humidity 35 to 85%RH, Storage: 35 to 85%RH

Insulation type

Double insulation or reinforced insulation 

(mark:  , dielectric strength between the measuring input part and the power part: 2kV)

Approval
Weight

2

Approx. 112g(approx. 74g) Approx. 176g(approx. 114g) Approx. 237g(approx. 152g)

 Ordering information

Unit

Sensor input type

Control output

Power supply

Control method

Size

Item

Temperature 

range

for each sensor

C

Celsius(

)

F

Fahrenheit(

)

Celsius(

) Fahrenheit(

) Temperature sensor

0

-50 to 100 -58 to 212

Pt

-

-

1

0 to 100

32 to 212

Pt

-

K

2

0 to 200

32 to 392

Pt

J

K

3

0 to 300

32 to 572

-

J

-

4

0 to 400

32 to 752

Pt

J

K

6

0 to 600

32 to 1,112

-

-

K

8

0 to 800

32 to 1,472

-

-

K

C

0 to 1,200 32 to 2,192

-

-

K

P

DPt100Ω

J

J(IC)

K

K(CA)

R

Relay output

S

SSR drive output

4

100-240VAC 50/60Hz

B

ON/OFF control & PID control combined

S

DIN W48 x H48mm(8 pin plug type)

1

M

DIN W72 x H72mm

L

DIN W72 x H72mm

TA

Analog setting type temperature controller

TA S

B 4 R P 4 C

1: 

Socket(PG-08, PS-08) is sold separately.

 Specification

 Front panel Identification

1

2

3

4

5

6

7

8

3. PID Control

PID constants are suggested and implemented based on self tuning from supply power until reaching set 

temperature(SV), then self tuning is over after reaching set temperature(SV). When power supply, in case that 

set temperature(SV) dial points at OFF or self tuning can not be started because present temperature(PV) is 

higher than set temperature(SV) or hunting occurs during self tuning, output control is switched to proportion 

band(P) because that is considered to error. At that time, proportion band is fixed at 10

.

Control cycle of PID control and proportion control is 20 sec. in relay output model and 2 sec. in SSR drive 

output model.   

4. STOP

Control output could stop without power off by setting the front setting volume to below min. setting range.

If control output stops by STOP function, green indicator in deviation indicator( ) will flash every 1 sec. 

5. Error

Error mark will flash(every 1 sec.) in PV indicator when error occurs during the control operation.

It will operate normally, if input sensor is connected or temperature is returned to normal range.  

No

Display

Description

1

 +   +   indicators flash

If input sensor is broken or sensor is not connected.

2

               indicator flashes

If measured sensor input is higher than temperature range.

3

                indicator flashes

If measured sensor input is lower than temperature range.

2. ON/OFF control

ON/OFF control function is for controlling temperature by comparing 

present temperature(PV) to set temperature(SV). ON/OFF control is 

fixed on reverse operation(Heating). Output turns on to supply power 

temperature(SV) and the output turns off to turn off heater when present 

temperature(PV) is higher then set temperature(SV). 

Hysteresis is fixed at 2

 during ON/OFF control.

1. SSR drive output 

 Functions

INPUT

SSR drive output

12VDC

LOAD

SSR module

SRH1 Series

Temperature

controller

Load

Power

Power

Reverse operation

(Heating)

Control output

Temperature

Hysteresis

SV

1. TAS Series

Mount the product on the panel and securely push the bracket in using a tool, as shown in the diagram.

2. TAM, TAL Series 

 Installation

1. TAS Series 

2. TAM Series

3. TAL Series

RTD(Platinum resistance thermometer): DPt100Ω(3-wire)          

T.C.(Thermocouple): K(CA), J(IC)

 Connections

RELAY OUT

250VAC 3A 1c

RESISTIVE LOAD

SOURCE

100-240VAC

4VA 50/60Hz

SSR

12VDC±2V

20mA Max

SENSOR

COM

RTD

N.C.

N.O.

B'

B

A

1

4

8

5

7

6

2

3

RELAY OUT

250VAC 3A 1c

RESISTIVE LOAD

SOURCE

100-240VAC

4VA 50/60Hz

SSR

12VDC±2V

20mA Max

SENSOR

COM

RTD

A

B

B'

T.C.

N.C.

N.O.

1

19

10

3

21

12

5

23

14

7

25

16

9

27

18

2

20

11

4

22

13

6

24

15

8

26

17

RELAY OUT

250VAC 3A 1c

RESISTIVE LOAD

SOURCE

100-240VAC

4VA 50/60Hz

SSR

12VDC±2V

20mA Max

SENSOR

COM

RTD

A

B

B'

T.C.

N.C.

N.O.

1

25

13

3

27

15

5

29

17

7

31

19

9

33

21

11

35

23

2

26

14

4

28

16

6

30

18

8

32

20

10

34

22

12

36

24

 Photoelectric sensors

 Temperature controllers

 Fiber optic sensors

 Temperature/Humidity transducers

 Door sensors

 SSR/Power controllers

 Door side sensors

 Counters 

 Area sensors

 Timers

 Proximity sensors

 Panel meters

 Pressure sensors

 Tachometer/Pulse(Rate) meters

 Rotary encoders

 Display units

 Connector/Sockets

 Sensor controllers

 Switching mode power supplies
 Control switches/Lamps/Buzzers
 I/O Terminal Blocks & Cables
 Stepper motors/drivers/motion controllers
 Graphic/Logic panels
 Field network devices
 Laser marking system(Fiber, CO

, Nd:YAG)

 Laser welding/soldering system

http://www.autonics.com

Satisfiable Partner For Factory Automation

 HEAD QUARTERS:

116, Ungbigongdan-gil, Yangsan-si, Gyeongsangnam-do, Korea

 OVERSEAS SALES: 

#402-404, Bucheon Techno Park, 655, Pyeongcheon-ro, 

Wonmi-gu, Bucheon, Gyeonggi-do, Korea

TEL: 82-32-610-2730 / FAX: 82-32-329-0728

 E-mail:

 [email protected]

The proposal of a product improvement and 

development: [email protected]

EP-KE-03-0340C

PV deviation temperature

Deviation indicator

Input sensor OPEN

▲ +  

 +  ▼ indicators flash(every 0.5 sec.)

Exceed max. input value

▲                  

  

indicator flashes(every 0.5 sec.)

More than 10

▲                   

  

indicator turns ON

More than 2

 to less than or equal to 10

▲ +          

  

indicators turn ON

Less than or equal to ±2

                

  

indicator turns ON

More than -2

 to less than or equal to -10

          

 +

▼ indicators turn ON

More than -10

                   

▼ indicator turns ON

Less than min. input value

                    

▼ indicator flashes(every 0.5 sec.)

(

Socket(PG-08, PS-08) is sold separately.)

1. TAS Series

 Dimensions

2. TAM Series

3. TAL Series

Size

Series

A

B

C

D

TAS

Min. 65

Min. 65

45

45

TAM

Min. 90

Min. 90

68

68

TAL

Min. 115 Min. 115 92

92

0.6

 0

0.7

 0

0.8

 0

0.6

 0

0.7

 0

0.8

 0

 Panel cut-out

A

C

D

B

 Terminal cover(sold separately)

 RMA-COVER(72×72mm)

70

68.5

3

64

13

 RLA-COVER(96×96mm )

91.5

86

3

13

94

 Bracket

 TAS Series

 TAM, TAL Series

46

23.9

12

37.5 40.5

3.3

4

31

20

15

21

5

16

36

56

55

45

□48.6

44.9

66.7

44.8

52

14

5.2

48

72

14.7

64.5

6.5

96

14.7

64.5

6.5

T.C.

Отзывы: