9 Appendix
© Copyright Reserved Autonics Co., Ltd.
97
9.2
CAN Memory Mapping
9.2.1
Overview
Due to the characteristic of DeviceNet, there is only a part that sets the output value of the
output device.
However, since the LP must knowthe current value even if it is output device, it consists of
‘output device command area’ for setting the output value and ‘output device current value area’
for checking the current value.
(1)
Input device area
Area where modules for input from Slave connected to DeviceNet are assigned
Size: 512byte=(max. number of connectable Slaves (63)+1)×Memory size per Slave (8byte)
Address: UW65536 ~ UW65791
(2)
Output device command area
Area assigned to set the output value on the module for the output of Slave connected to
DeviceNet
Size: 512byte=(max. number of connectable Slaves (63)+1)×Memory size per Slave (8byte)
Address: UW65792 ~ UW66047
(3)
Output device current value area
Area assigned to read the current value of the module for the output of Slave connected to
DeviceNet
Size: 512byte=(max. number of connectable Slaves (63)+1)×Memory size per Slave (8byte)
Address: UW66048 ~ UW66303
Содержание LP-A Series
Страница 2: ...ii Copyright Reserved Autonics Co Ltd ...
Страница 27: ...1 Overview Copyright Reserved Autonics Co Ltd 27 1 8 Dimension 1 8 1 LP A070 unit mm ...
Страница 28: ...1 Overview 28 Copyright Reserved Autonics Co Ltd 1 8 2 LP A104 unit mm ...
Страница 29: ...1 Overview Copyright Reserved Autonics Co Ltd 29 1 8 3 Common ...
Страница 30: ...1 Overview 30 Copyright Reserved Autonics Co Ltd ...
Страница 38: ...2 Installation 38 Copyright Reserved Autonics Co Ltd ...
Страница 46: ...3 System Organization 46 Copyright Reserved Autonics Co Ltd ...
Страница 66: ...6 Troubleshooting 66 Copyright Reserved Autonics Co Ltd ...
Страница 70: ...7 Repair Maintenance Inspection 70 Copyright Reserved Autonics Co Ltd ...
Страница 105: ...9 Appendix Copyright Reserved Autonics Co Ltd 105 ...