2 Modbus Mapping Table 

© Copyright Reserved Autonics Co., Ltd. 

 

21 

2.4.3

 

Parameter 2 group[Func: 03/06/16, RW: R/W] 

No(Address) 

Parameter  Description 

Set range 

Unit 

Factory default 

400101(0064) 

AT 

Auto-tuning RUN/STOP 

0 : 

OFF   

1 :

 ON

 

OFF 

400102(0065) 

H-P 

Heating, proportional band 

1 to 9999: 

00)1

 to 

99(9

 

/

/% 

010.0 

400103(0066) 

C-P 

Cooling, proportional band 

400104(0067) 

H-I 

Heating, integral time 

0 to 9999: 

0000

 to 

9999

 

sec. 

0000 

400105(0068) 

C-I 

Cooling, integral time 

400106(0069) 

H-D 

Heating, derivative time 

0 to 9999: 

0000

 to 

9999

 

sec. 

0000 

400107(006A) 

C-D 

Cooling, derivative time 

400108(006B) 

DB 

Heating/Cooling, Dead band 

-proportional band to 

)0

 to +proportional 

band 
(based on small value of proportional band) 
 
<ON/OFF – ON/OFF control> 

-999

 to 

0999

 (H) 

`9(9

 to 

99(9

 (L) 

Digit 

0000 

-9(9 to    09(9 (analog) 

%F.S 

000.0 

400109(006C) 

REST 

Proportional controlling, 

Manual reset 

0 to 1000: 

00)0 to 10)0

 

05)0 

400110(006D) 

hHYS 

Heating, hysteresis 

1 to 100: 

001

 to 

100

(temperature H, 

analog) 
1 to 1000: 

00)1

 to 

10)0

(temperature L) 

Digit 

002 

400111(006E) 

hOST 

Heating, OFF offset 

0 to 100: 

000

 to 

100

(temperature H, 

analog) 
0 to 1000: 

00)0

 to 

10)0

(temperature L) 

Digit 

000 

400112(006F) 

cHYS 

Cooling, hysteresis 

1 to 100: 

001

 to 

100

(temperature H, 

analog) 
1 to 1000: 

00)1

 to 

10)0

(temperature L) 

Digit 

002 

400113(0070) 

cOST 

Cooling, OFF offset 

0 to 100: 000 to 100(temperature H, 

analog) 
0 to 1000: 

00)0

 to 

10)0

(temperature L) 

Digit 

000 

400114(0071) 

L-MV 

MV low-limit set value 

00)0

 to 

H-MV - )1

 (standard control) 

`0)0

 to 

00)0

 (Heating/Cooling) 

000.0 
`00.0 

400115(0072) 

H-MV 

MV high-limit set value 

L-MV 

+

+ )1

 to 

10)0

 (standard control) 

00)0

 to 

10)0

 (Heating/Cooling) 

10)0 
10)0 

400116(0073) 

RAMU 

Lamp Up-change rate 

0 to 999: 

000

 to 

999

(temperature H, 

analog) 
0 to 9999: 

00)0

 to 

99(9

(temperature L) 

Digit 

000 

400117(0074) 

RAMD 

Lamp Down-change rate 

0 to 999: 

000

 to 

999

(temperature H, 

analog) 
0 to 9999: 

00)0

 to 

99(9

(temperature L) 

Digit 

0000 

400118(0075) 

rUNT 

Lamp time unit 

0 : 

SEC

  1 : 

MIN

  2 : 

HOUR

 

MIN 

Reserved 

 

 

 

Содержание KPN Series

Страница 1: ...re Controllers KPN Series ACM E 0301 AB Thank you for purchasing an Autonics product This user manual contains information about the product and its proper use and should be kept in a place where it w...

Страница 2: ...Preface 2 Copyright Reserved Autonics Co Ltd...

Страница 3: ...ng Autonics product Please familiarize yourself with the information contained in the Safety Precautions section before using this product This user manual contains information about the product and i...

Страница 4: ...r reproduced in either part or whole without permission A user manual is not provided as part of the product package Visit our web site www autonics com to download a copy The manual s content may var...

Страница 5: ...Communication protocol Copyright Reserved Autonics Co Ltd 5 Communication protocol KPN Series is supported to Modbus RTU protocol However it does not support broadcast commands...

Страница 6: ...Communication protocol 6 Copyright Reserved Autonics Co Ltd...

Страница 7: ...10H 14 1 7 Exception Response Error Code 15 2 Modbus Mapping Table 17 2 1 Read Coils Func01 Write Single Coil Func05 17 2 2 Read Discrete Inputs Func02 17 2 3 Read Input Registers Func04 18 2 4 Read H...

Страница 8: ...Table of Contents 8 Copyright Reserved Autonics Co Ltd...

Страница 9: ...1Byte 1Byte 1Byte 1Byte 1Byte If read the output status ON 1 OFF 0 of 10EA within coil 000001 0000 H to 000010 0009 H on Slave side Address 17 from Master side Query Master Slave Address Function Star...

Страница 10: ...yte 1Byte 1Byte 1Byte If read the input status ON 1 OFF 0 of 10EA range 100001 0000 H to 100010 0009 H in the Slave side Address 17 from the Master side Query Master Slave Address Function Starting Ad...

Страница 11: ...igh Low High Low High Low Low High 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte If read the values of 2EA from Holding Register 400001 0000 H to 400002 0001 H in Slave Address 17...

Страница 12: ...CRC16 Low High 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte If read the values of 2EA range from Input Register 300001 0000 H to 300002 0001 H on Slave side Address 17 from Master side Query Master...

Страница 13: ...sponse Slave Slave Address Function Register Address Preset Data Error Check CRC16 High Low High Low Low High 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte If write 10 A H to Holding Register 400001...

Страница 14: ...in common to the range of Holding Register 400001 0000 H to 400002 0001 H on Slave side Address 17 from Master side Query Master Slave Address Function Starting Address No of Register Byte Count Data...

Страница 15: ...data is inconsistent with transmittable address from the device ILLRGAL DATA VALUE Exception Code 03 H The number of queried data are inconsistent with the numbers of transmittable transferable data f...

Страница 16: ...1 Modbus RTU protocol 16 Copyright Reserved Autonics Co Ltd...

Страница 17: ...100003 0002 lamp 0 OFF 1 ON 100004 0003 OUT1 lamp Control output1 display lamp 0 OFF 1 ON 100005 0004 OUT2 lamp Control output2 display lamp 0 OFF 1 ON 100006 0005 AT lamp Auto tuning RUNlamp 0 OFF 1...

Страница 18: ...eserved 300117 0074 Reserved 300118 0075 Coil status start Address 0000 300119 0076 Coli status Quantity 0 300120 0077 Input status start Address 0000 300121 0078 Input status Quantity 0 300122 0079 H...

Страница 19: ...splay lamp 0 OFF 1 ON Bit A AL3 lamp Alarm output3 display lamp 0 OFF 1 ON Bit B MAN lamp Manual control display lamp 0 OFF 1 ON Bit C DI 1 input DI 1 input status 0 OFF 1 ON Bit D DI 2 input DI 2 inp...

Страница 20: ...ss Parameter Description Set range Unit Factory default 400051 0032 R S Control output RUN STOP 0 RUN 1 STOP RUN 400052 0033 SV N Multi SV No 0 SV 0 1 SV 1 2 SV 2 3 SV 3 SV 0 400053 0034 CT A Heater c...

Страница 21: ...0 05 0 400110 006D hHYS Heating hysteresis 1 to 100 001 to 100 temperature H analog 1 to 1000 00 1 to 10 0 temperature L Digit 002 400111 006E hOST Heating OFF offset 0 to 100 000 to 100 temperature...

Страница 22: ...MAvF Input digital filter 1 to 1200 00 1 to 12 0 sec 00 1 400161 00A0 L SV SV low limit set value Input low limit value L SC to H SV 1Digit F S 200 00 0 400162 00A1 H SV SV high limit set value L SV...

Страница 23: ...0 0000 to 3600 sec 0000 400212 00D3 A OF Alarm output2 OFF delay time 0 to 3600 0000 to 3600 sec 0000 400213 00D4 AL 3 Alarm output3 mode 0 OFF 1 DVCC 2 DV 3 DVC 4 CDV 5 PVCC 6 PV 7 LBA 8 SBA 9 HBA LB...

Страница 24: ...100 to 5 000 100 to 000 1 000 400258 0101 BAR Bar graph 0 OFF 1 OUT1 standard 0 OFF 1 OUT1 2 OUT2 3 ALL heating cooling OUT1 400259 0102 Manual control initial MV 0 AUTO 1 PrMV ALL 400260 0103 ItMV Ma...

Страница 25: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 25...

Страница 26: ...Dimensions or specifications on this manual are subject to change and some models may be discontinued without notice...

Отзывы: