2 Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd.
21
2.4.3
Parameter 2 group[Func: 03/06/16, RW: R/W]
No(Address)
Parameter Description
Set range
Unit
Factory default
400101(0064)
AT
Auto-tuning RUN/STOP
0 :
OFF
1 :
ON
-
OFF
400102(0065)
H-P
Heating, proportional band
1 to 9999:
00)1
to
99(9
℃
/
℉
/%
010.0
400103(0066)
C-P
Cooling, proportional band
400104(0067)
H-I
Heating, integral time
0 to 9999:
0000
to
9999
sec.
0000
400105(0068)
C-I
Cooling, integral time
400106(0069)
H-D
Heating, derivative time
0 to 9999:
0000
to
9999
sec.
0000
400107(006A)
C-D
Cooling, derivative time
400108(006B)
DB
Heating/Cooling, Dead band
-proportional band to
)0
to +proportional
band
(based on small value of proportional band)
<ON/OFF – ON/OFF control>
-999
to
0999
(H)
`9(9
to
99(9
(L)
Digit
0000
-9(9 to 09(9 (analog)
%F.S
000.0
400109(006C)
REST
Proportional controlling,
Manual reset
0 to 1000:
00)0 to 10)0
%
05)0
400110(006D)
hHYS
Heating, hysteresis
1 to 100:
001
to
100
(temperature H,
analog)
1 to 1000:
00)1
to
10)0
(temperature L)
Digit
002
400111(006E)
hOST
Heating, OFF offset
0 to 100:
000
to
100
(temperature H,
analog)
0 to 1000:
00)0
to
10)0
(temperature L)
Digit
000
400112(006F)
cHYS
Cooling, hysteresis
1 to 100:
001
to
100
(temperature H,
analog)
1 to 1000:
00)1
to
10)0
(temperature L)
Digit
002
400113(0070)
cOST
Cooling, OFF offset
0 to 100: 000 to 100(temperature H,
analog)
0 to 1000:
00)0
to
10)0
(temperature L)
Digit
000
400114(0071)
L-MV
MV low-limit set value
00)0
to
H-MV - )1
(standard control)
`0)0
to
00)0
(Heating/Cooling)
%
000.0
`00.0
400115(0072)
H-MV
MV high-limit set value
L-MV
+
+ )1
to
10)0
(standard control)
00)0
to
10)0
(Heating/Cooling)
%
10)0
10)0
400116(0073)
RAMU
Lamp Up-change rate
0 to 999:
000
to
999
(temperature H,
analog)
0 to 9999:
00)0
to
99(9
(temperature L)
Digit
000
400117(0074)
RAMD
Lamp Down-change rate
0 to 999:
000
to
999
(temperature H,
analog)
0 to 9999:
00)0
to
99(9
(temperature L)
Digit
0000
400118(0075)
rUNT
Lamp time unit
0 :
SEC
1 :
MIN
2 :
HOUR
-
MIN
e
Reserved
Содержание KPN Series
Страница 2: ...Preface 2 Copyright Reserved Autonics Co Ltd...
Страница 6: ...Communication protocol 6 Copyright Reserved Autonics Co Ltd...
Страница 8: ...Table of Contents 8 Copyright Reserved Autonics Co Ltd...
Страница 16: ...1 Modbus RTU protocol 16 Copyright Reserved Autonics Co Ltd...
Страница 25: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 25...