2 Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd.
17
2
Modbus Mapping Table
2.1
Read Coils(Func01) / Write Single
Coil(Func05)
No(Address)
Type
Description
Set range
Unit
Factory default
000001(0000)
RUN/STOP
Control output RUN/STOP
0:
RUN
1:
STOP
-
RUN
000002(0001)
Auto-tuning
RUN/STOP
Auto-tuning RUN/STOP
0:
OFF
0:
ON
-
OFF
000003 to 000050 Reserved
2.2
Read Discrete Inputs(Func02)
No(Address)
Type
Description
Set range
Unit
Factory default
100001(0000)
℃
lamp
Unit display lamp
0: OFF 1: ON
-
-
100002(0001)
℉
lamp
0: OFF 1: ON
-
-
100003(0002)
% lamp
0: OFF 1: ON
-
-
100004(0003)
OUT1 lamp
Control output1 display lamp 0: OFF 1: ON
-
-
100005(0004)
OUT2 lamp
Control output2 display lamp 0: OFF 1: ON
-
-
100006(0005)
AT lamp
Auto-tuning RUNlamp
0: OFF 1: ON
-
-
100007(0006)
SV1 lamp
Multi-SV1 lamp
0: OFF 1: ON
-
-
100008(0007)
SV2 lamp
Multi-SV2 lamp
0: OFF 1: ON
-
-
100009(0008)
SV3 lamp
Multi-SV3 lamp
0: OFF 1: ON
-
-
100010(0009)
AL1 lamp
Alarm output1 display lamp
0: OFF 1: ON
-
-
100011(000A)
AL2 lamp
Alarm output2 display lamp
0: OFF 1: ON
-
-
100012(000B)
AL3 lamp
Alarm output3 display lamp
0: OFF 1: ON
-
-
100013(000C)
MAN lamp
Manual control display lamp 0: OFF 1: ON
100014(000D)
DI-1 input
DI-1 input status
0: OFF 1: ON
-
-
100015(000E)
DI-2 input
DI-2 input status
0: OFF 1: ON
-
-
100016 to
100050
Reserved
Содержание KPN Series
Страница 2: ...Preface 2 Copyright Reserved Autonics Co Ltd...
Страница 6: ...Communication protocol 6 Copyright Reserved Autonics Co Ltd...
Страница 8: ...Table of Contents 8 Copyright Reserved Autonics Co Ltd...
Страница 16: ...1 Modbus RTU protocol 16 Copyright Reserved Autonics Co Ltd...
Страница 25: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 25...