1 Modbus RTU protocol
© Copyright Reserved Autonics Co., Ltd.
13
1.5
Preset Single Registers(Func06–06H)
Read the Binary data of single Holding Registers (4X reference) in Slave device.
(1)
Query(Master)
Slave Address Function
Register Address
Preset Data
Error Check(CRC16)
High
Low
High
Low
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
(2)
Response(Slave)
Slave Address Function
Register Address
Preset Data
Error Check(CRC16)
High
Low
High
Low
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
If write
“10(
A H
)” to
Holding Register
400001(0000
H
) on
Slave
(
Address
17) from
Master
.
Query
(Master)
Slave Address Function
Starting Address
Preset Data
Error Check(CRC16)
High
Low
High
Low
Low
High
11 H
06 H
00 H
00 H
00 H
0A H
## H
## H
Response
(Slave)
Slave Address Function
Starting Address
Preset Data
Error Check(CRC16)
High
Low
High
Low
Low
High
11 H
06 H
00 H
00 H
00 H
0A H
## H
## H
CRC16
CRC16