1 Modbus RTU protocol
10
© Copyright Reserved Autonics Co., Ltd.
1.2
Read Input Status(Func02–02H)
Read Input ON/OFF status(1X reference) in Slave device.
(1)
Query(Master)
Slave Address Function
Starting Address
No. of Points
Error Check(CRC16)
High
Low
High
Low
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
(2)
Response(Slave)
Slave Address Function
Byte Count
Data
Data
Data
Error Check(CRC16)
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
If read the input status(ON: 1, OFF: 0) of 10EA range 100001(0000 H) to 100010(0009 H)
in the Slave side (Address 17) from the Master side.
Query(Master)
Slave Address Function
Starting Address
No. of Points
Error Check(CRC16)
High
Low
High
Low
Low
High
11 H
02 H
00 H
00 H
00 H
0A H
## H
## H
If the values range 100008(0007 H) to 100001(0000 H) on slave side are “ON-ON-OFF-
OFF-ON-ON-OFF-ON”, and the values of 100010(0009 H) to 100009(0008 H) are
respectively “OFF-ON”.
Response(Slave)
Slave Address Function
Byte Count
Data
(000008 to
000001)
Data
(000010 to
000009)
Error Check(CRC16)
Low
High
11 H
02 H
02 H
CD H
01 H
## H
## H
CRC16
CRC16
Содержание KPN Series
Страница 2: ...Preface 2 Copyright Reserved Autonics Co Ltd...
Страница 6: ...Communication protocol 6 Copyright Reserved Autonics Co Ltd...
Страница 8: ...Table of Contents 8 Copyright Reserved Autonics Co Ltd...
Страница 16: ...1 Modbus RTU protocol 16 Copyright Reserved Autonics Co Ltd...
Страница 25: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 25...