9.ModbusMappingTable
49
©CopyrightReservedAutonicsCo.,Ltd.
9.ModbusMappingTable
9.1
Functioncode3(0X03)=Readholdingresisters
(1)Request
(2)Response
(2)Response
※
Exception code
0×01 : Not supported command code.
0×02 : Starting address of required data and transmittable address are different.
0×03 : The number of required data is over than the number of transmittable data.
0×04 : Transmittable data does not process properly.
9.2
Functioncode4(0×04)=Readinputresisters
(1)Request
※
Exception code
0×01 : Not supported command code.
0×02 : Starting address of required data and transmittable address are different.
0×03 : The number of required data is over than the number of transmittable data.
0×04 : Transmittable data does not process properly.
(3)Error
(3)Error
Master to Slave
Master to Slave
Slave to Master
Slave to Master
Slave to Master
Slave to Master
0×01
0×03
0×00
0×00
0×00
0×16
××
××
Add.
Com-
mand
Start address
Number of data
CRC 16
High
Low
High
Low
High
Low
0×01
0×03
0×10
0×03
0×E8
...
0×03
0×E8
××
××
Add.
Response
command
Number of
data
1st data
...
16th data
CRC 16
High
Low
...
High
Low
High
Low
0×01
0×83
××
××
××
Address
Response
command
Exception
code
CRC 16
0×01
0×04
0×00
0×00
0×00
0×10
××
××
Address
Command
Start address
Number of data
CRC 16
High
Low
High
Low
High
Low
0×01
0×84
××
××
××
Address
Response
command
Exception
code
CRC 16
0×01
0×04
0×10
0×03
0×E8
... 0×03
0×E8
××
××
Address Response
command
Number
of data
1st data
... 16th data
CRC 16
High
Low
... High
Low
High
Low
Содержание Digipower 2000
Страница 2: ... ii Copyright Reserved Autonics Co Ltd ...
Страница 8: ...Safety Precautions viii Copyright Reserved Autonics Co Ltd ...
Страница 14: ...1 Product introduction 14 Copyright Reserved Autonics Co Ltd ...
Страница 26: ...5 Installation and initial operation 26 Copyright Reserved Autonics Co Ltd ...
Страница 46: ...7 Factory default 46 Copyright Reserved Autonics Co Ltd ...
Страница 54: ...9 Modbus Mapping Table 54 Copyright Reserved Autonics Co Ltd ...