6.3
Alarm
※
1: When it cannot return by re-supplying power because fuse is disconnected or element is
error, refer to ‘8. Maintenance’.
6.3.1
Overcurrent alarm [
OC-A
]
When overcurrent alarm occurs, output stops and alarm maintains. [
O-C
] flashes for 0.5 sec in the
display part and the EVT indicator flashes for 0.5 sec.
When setting as [
NON
], alarm output does not occur but [
O-C
] flashes.
Alarm clears when re-supplying power, reset, or stop the unit.
(1) Overcurrent alarm value setting [
OC-U
]
Set overcurrent alarm value within 0.0 to 120.0% of rated current range.
(2) Overcurrent alarm delay time [
OC-T
]
Set overcurrent alarm delay time within 0 to 100 sec. range. After the set time, over current alarm
occurs.
6.3.2
Current limit [
C-LM
]
This function limits current when using big inrush load to protect thyristor.
Especially for voltage feedback, current for load resistance value flows and it may over the rated
thyristor only voltage control. Therefore, it limits current to prevent over the rated current.
• Set range: 0 to 110% (unit: %)
Alarm
Display
Operation in alarm
Alarm clear
Overcurrent alarm
O-C
Stops output
(SCR OFF)
•
Re-supply the power.
•
RESET (
key)
•
Switch to STOP mode
Overvoltage alarm
O-V
Fuse break alarm
FUSE
Heatsink overheat alarm
TEMP
Element error alarm
SCR
Heater break alarm
H-BK
Continues operation
Automatically cleared within
the set range
※
1
※
1
Содержание Digipower 2000
Страница 2: ... ii Copyright Reserved Autonics Co Ltd ...
Страница 8: ...Safety Precautions viii Copyright Reserved Autonics Co Ltd ...
Страница 14: ...1 Product introduction 14 Copyright Reserved Autonics Co Ltd ...
Страница 26: ...5 Installation and initial operation 26 Copyright Reserved Autonics Co Ltd ...
Страница 46: ...7 Factory default 46 Copyright Reserved Autonics Co Ltd ...
Страница 54: ...9 Modbus Mapping Table 54 Copyright Reserved Autonics Co Ltd ...