Electrician
The A35M meter should only be installed by a fully qualified electrician who has
knowledge of electricity meters connected with current transformers.
It is the installer who is fully responsible for the safe installation of this meter. It must be
installed to meet the current electrical regulations concerning installation of meters.
EMC Installation Requirements
Whilst this unit complies with all relevant EU EMC (electro-magnetic compatibility)
regulations, any additional precautions necessary to provide proper operation of this and
adjacent equipment will be installation dependent and so the following can only be
general guidance:
Avoid routing wiring to this unit alongside cables and products that are, or could be, a
source of interference.
The supply to the unit should not be subject to excessive interference. In some cases, a
supply line filter may be required.
To protect the product against incorrect operation or permanent damage, surge
transients must be controlled. It is good EMC practice to suppress transients and surges
at the source. The unit has been designed to automatically recover from typical
transients; however in extreme circumstances it may be necessary to temporarily
disconnect the supply for a period of greater than 10 seconds to restore correct
operation.
Screened communication leads are recommended and may be required. These and other
connecting leads may require the fitting of RF suppression components, such as ferrite
absorbers, line filters etc., if RF fields cause problems.
It is good practice to install sensitive electronic instruments that are performing critical
functions in EMC enclosures that protect against electrical interference causing a
disturbance in function.
Password Entry
Wiring Information
Power Supply
The Auxiliary connection must be connected to power up the meter.
Wiring
Electrical and communication connections are made directly to the front of the meter.
Electrical Connections
2.5mm flexible stranded cable is recommended for all main electrical connections. For the
low voltage communication connections we recommend a twisted shielded cable Belden
9841 2 wire or 9842 4 wire or equivalent.
Phasing and polarity of the AC current and voltage inputs and their relationship is critical to
the correct operation.
Programming the meter
When you receive the meter
there will be at least one value
that you must programme into
the meter. This is the current
transformer ratio.
If the m
eter has been purchased with the intention of using the RS 485
Modbus output then you will have to program the Modbus parameters you
require. See reverse Communication. (RS 485 Modbus)
Pulse Definition
The pulse outputs can be set to generate pulses to
represent kWh/kVarh
Pulse constant: 0.001/0.01/0.1/1/10/100/1000 kWh or
kVarh per Pulse
Pulse width: 200/100/60 Ms.
The pulse output is passive type, complies with
IEC62053-31 Class A.
ATTENTION:
Pulse output must be wired as shown in
the wiring diagram below. Scrupulously respect
polarties and the connection mode. Opto-coupler with
potential-free SPST-No Contact.
Contact range: 5~27VDC Max. current Input: 27mADC
A-35M
METER
3 PHASE 4 WIRE
U
imp
R
OUTPUT
P+
Com
Pulse Rate (Energy Value per Pulse)
Pulse rate options: 0.001 , 0.01 , 0.1 , 1, 10, 100, 1000 kWh /
kVarh per Pulse. Default : 0.01 kWh (100imp/kWh)
Use and t
o select Pulse Rate option.
Long press t
he setting will flash.
Use and t
o choose Options.
Long press fo
r confirmation.
P
MD
PF Hz
P
MD
PF Hz
E
E
To Enter programing mode.
Press for 3 seconds
Display will show pass
0000
The first digit will flash.
Press once to increment the number to 1
Press and hold down to enter program mode.
Press to scroll down to programme various
parameters
E
MD
PF Hz
E
P
Pulse Output
This option allows you to configure the pulse output. The
output can be set to provide a pulse for a defined amount
of energy active or reactive. Use this section to set up the
pulse output—Units: kWh, kVArh
From the set-up menu, use and buttons to select
the Pulse output option.
Press to enter the selection routine. The unit symbol will
flash.
Use and buttons to choose kWh or kVArh.
On completion of the entry procedure, press to confirm
the setting and press to return to the main set up menu.
MD
PF Hz
P
MD
PF Hz
P
E
E
V/A
IMPORTANT
Current transformer
P1 must face mains
LOAD
MAINS
S2 S1
P2