Appendix
A
Auxiliary
Functions
A--7
Auxilliary Functions
DL105 PLC User Manual, 3rd Edition
AUX 7* — EEPROM Operations
The following auxiliary functions allow you to move the ladder program from one
area to another and perform other program maintenance tasks.
Many of these AUX functions allow you to copy different areas of memory to and
from the CPU and handheld programmer. The following table shows the areas that
may be mentioned.
Option and Memory Type
DL105 Default Range
1:PGM — Program
$00000 -- $02047
2:V — V--memory
$00000 -- $03777
3:SYS — System
Non-selectable copies
system parameters
4:etc (All)— Program, Sys-
tem and
non-volatile
V--
memory only
Non-selectable
AUX 71 copies information from the CPU memory to an EEPROM installed in the
Handheld Programmer.You can copy different portions of EEPROM (HP) memory to
the CPU memory as shown in the previous table.
AUX 72 copies information from the EEPROM installed in the Handheld
Programmer to CPU memory in the DL105. You can copy different portions of
EEPROM (HP) memory to the CPU memory as shown in the previous table.
AUX 73 compares the program in the Handheld programmer (EEPROM) with the
CPU program. You can compare different types of information as shown previously.
AUX 74 allows you to check the EEPROM in the handheld programmer to make sure
it is blank. It’s a good idea to use this function anytime you start to copy an entire
program to an EEPROM in the handheld programmer.
AUX 75 allows you to clear all data in the EEPROM in the handheld programmer.
You should use this AUX function before you copy a program from the CPU.
You can use AUX 76 to quickly determine what size EEPROM is installed in the
Handheld Programmer.
Transferrable
Memory Areas
AUX 71
CPU to HPP
EEPROM
AUX 72
HPP EEPROM
to CPU
AUX 73
Compare HPP
EEPROM to CPU
AUX 74
HPP EEPROM
Blank Check
AUX 75
Erase HPP
EEPROM
AUX 76
Show EEPROM
Type
Содержание DL105
Страница 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Страница 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Страница 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Страница 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Страница 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...
Страница 329: ...1F European Union Directives CE In This Appendix European Union EU Directives Basic EMC Installation Guidelines...