Automationdirect.com Productivity 2000 P2-08TAS Скачать руководство пользователя страница 1

®

P2-08TAS AC 

Isolated Output

 

Sales 800-633-0405 

www.productivity2000.com 

1

Output Specifications

Outputs per Module 

8  

Rated Voltage

100–120 VAC

Operating Voltage Range

85–132 VAC

AC Frequency

47–63 Hz

Maximum Output Current

1A / point @ 40°C 

0.7 A / point @ 60°C

Minimum Load Current

10mA

Maximum Leakage Current  

4mA @ 144VDC

On Voltage Drop

1.5 VAC @ > 50mA 

 

4.0 VAC @ < 50mA

Maximum Inrush Current 

3A for 10ms

OFF to ON Response 

1ms + 1/2 cycle

ON to OFF Response 

1ms + 1/2 cycle

Status Indicators 

Logic Side (8 points)

Commons 

8 Isolated (1 point / common) 

Recommended External Fuse

1.6 A Max. (AutomationDirect P/N S5001-6-R)

The P2-08TAS AC Output Module provides 

eight 100–120 VAC isolated outputs for use 

with the Productivity2000 System.

Output Specifications   . . . . . . . . . . 1

Module Installation Procedure . . . . 2

Terminal Block Removal  . . . . . . . . 2

Hot Swap Information  . . . . . . . . . . 2

Wiring Options . . . . . . . . . . . . . . . . 3

Schematic and Wiring Diagram . . . 3

Warning  . . . . . . . . . . . . . . . . . . . . . 4

Removable Terminal Block 

Specifications   . . . . . . . . . . . . . . . . 4

General Specifications   . . . . . . . . . 4

Warranty: Thirty-day money-back guarantee. Two-year limited replacement. 

(See www.productivity2000.com for details).

Terminal Block sold separately 

(see wiring options on page 3).

P2-08TAS

100-120VAC OUTPUT

C1

1

C2

2

C3

3

C4

4

C5

5

C6

6

C7

7

C8

8

Отзывы: