P2-08TAS AC
Isolated Output
Sales 800-633-0405
www.productivity2000.com
1
Output Specifications
Outputs per Module
8
Rated Voltage
100–120 VAC
Operating Voltage Range
85–132 VAC
AC Frequency
47–63 Hz
Maximum Output Current
1A / point @ 40°C
0.7 A / point @ 60°C
Minimum Load Current
10mA
Maximum Leakage Current
4mA @ 144VDC
On Voltage Drop
1.5 VAC @ > 50mA
4.0 VAC @ < 50mA
Maximum Inrush Current
3A for 10ms
OFF to ON Response
1ms + 1/2 cycle
ON to OFF Response
1ms + 1/2 cycle
Status Indicators
Logic Side (8 points)
Commons
8 Isolated (1 point / common)
Recommended External Fuse
1.6 A Max. (AutomationDirect P/N S5001-6-R)
The P2-08TAS AC Output Module provides
eight 100–120 VAC isolated outputs for use
with the Productivity2000 System.
Output Specifications . . . . . . . . . . 1
Module Installation Procedure . . . . 2
Terminal Block Removal . . . . . . . . 2
Hot Swap Information . . . . . . . . . . 2
Wiring Options . . . . . . . . . . . . . . . . 3
Schematic and Wiring Diagram . . . 3
Warning . . . . . . . . . . . . . . . . . . . . . 4
Removable Terminal Block
Specifications . . . . . . . . . . . . . . . . 4
General Specifications . . . . . . . . . 4
Warranty: Thirty-day money-back guarantee. Two-year limited replacement.
(See www.productivity2000.com for details).
Terminal Block sold separately
(see wiring options on page 3).
P2-08TAS
100-120VAC OUTPUT
C1
1
C2
2
C3
3
C4
4
C5
5
C6
6
C7
7
C8
8