![Automationdirect.com Productivity 1000 P1-08NA Скачать руководство пользователя страница 1](http://html1.mh-extra.com/html/automationdirect-com/productivity-1000-p1-08na/productivity-1000-p1-08na_manual_3021958001.webp)
1
Sales 800-633-0405
www.productivity1000.com
C1
2
3
4
C2
5
6
7
8
1
P1-08NA
100-240VAC
INPUT
1000
P1-08NA AC Input
The P1-08NA AC Input Module provides
eight 100–240 VAC inputs for use with the
Productivity1000 system.
Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Schematic & Wiring Diagram . . . . . . . . . . . . . . . . . . . .3
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . .4
Terminal Block Specifications . . . . . . . . . . . . . . . . . . . .4
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Terminal Block sold separately, (see wiring options on page 3).
Warranty: Thirty-day money-back guarantee. Two-year limited
replacement (See www.productivity1000.com for details).
Input Specifications
Inputs per Module
8
Rated Voltage
100–240 VAC
Operating Voltage Range
80–288 VAC
AC Frequency
47–63 Hz
Input Current
7mA @ 100VAC (50Hz)
8.5 mA @ 100VAC (60Hz)
14.2 mA @ 240VAC (50Hz)
17mA @ 240VAC (60Hz)
Maximum Input Current @ Temp
26mA @ 60°C (288VAC)
Input Impedance
15k
(50Hz), 12k
(60Hz)
ON Voltage Level
> 70VAC
OFF Voltage Level
< 20VAC
Minimum ON Current
5mA
Maximum OFF Current
2mA
OFF to ON Response
< 10ms
ON to OFF Response
< 25ms
Status Indicators
Logic Side (8 points)
Commons per module*
2 Isolated (4 points/common) @ 120VAC
2 Non-Isolated @ 240VAC
*C1 and C2 must be jumped together by an external wire during 240VAC applications.