Automationdirect.com Productivity 1000 P1-04THM Скачать руководство пользователя страница 1

1

Sales 800-633-0405

www.productivity1000.com

TC1+

TC2+

TC2-

TC3+

TC3-

TC4+

TC4-

TC1-

P1-04THM

THERMOCOUPLE

INPUT

1000

P1-04THM Analog Input

The P1-04THM Thermocouple Input Module 

provides  four  differential  channels  for  receiving 

thermocouple and voltage input signals for use with 

the Productivity1000 system.

Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . .  1

General Specifications  . . . . . . . . . . . . . . . . . . . . . .  2

Removable Terminal Block Specifications. . . . . . . .  2

Wiring Diagram and Schematic . . . . . . . . . . . . . . . .  3

Module Installation Procedure . . . . . . . . . . . . . . . . .  4

QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4

Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

Module Configuration  . . . . . . . . . . . . . . . . . . . . . . .  5

Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

Warranty: Thirty-day money-back guarantee. Two-year limited 

replacement (See www.productivity1000.com for details).

Terminal Block Included. Not Compatible with ZIPLink.

Thermocouple Input Specifications

Input Channels

4 differential

Data Format

Floating Point

Common Mode Range

±1.25 V

Common Mode Rejection

100dB @ DC

Input Impedance

>5M

Maximum Ratings

Fault Protected Inputs to ±50V

Resolution

16-bit, ±0.1 °C or °F

Thermocouple Input Ranges

Type J  -190° to 760°C (-310° to 1400°F)
Type E - 210° to 1000°C (-346° to 1832°F)
Type K  -150° to 1372°C (-238° to 2505°F)
Type R    65° to 1768°C (149° to 3214°F)
Type S    65° to 1768°C (149° to 3214°F)
Type T  -230° to 400°C (-382° to 752°F)
Type B   529° to 1820°C (984° to 3308°F)
Type N  -70° to 1300°C (-94° to 2372°F)
Type C   65° to 2320°C (149° to 4208°F)

Thermocouple Linearization

Automatic

Cold Junction Compensation

Automatic

Sample Duration Time

270ms

All Channel Update Rate

1.08 s

Open Circuit Detection Time

Within 5s

Conversion Method

Sigma-Delta

Accuracy vs. Temperature

±50ppm per °C (maximum)

Maximum Inaccuracy

±3°C maximum (excluding thermocouple error)

Linearity Error

±1°C maximum (±0.5 °C typical)
Monotonic with no missing codes

Warm-up Time

30 minutes for ±1% repeatability
2 minutes to reach voltage specifications

External Power Supply 

Required

None

Содержание Productivity 1000 P1-04THM

Страница 1: ...Mode Range 1 25 V Common Mode Rejection 100dB DC Input Impedance 5M Maximum Ratings Fault Protected Inputs to 50V Resolution 16 bit 0 1 C or F Thermocouple Input Ranges Type J 190 to 760 C 310 to 1400...

Страница 2: ...Solid Stranded Conductor 3 64 in 1 2 mm Insulation Max 19 64 in 7 8 mm Strip Length Conductors Use Thermocouple Extension wire for thermocouples USE COPPER CONDUCTORS 75 C or equivalent Screw Driver 0...

Страница 3: ...Grounded Shielded Thermocouple Infrared Thermocouple 4 wire Voltage Transmitter Load Cell or Strain Gauge Voltage Divider TC TC TC TC TC TC NOTES 1 Connect shield to thermocouple signal ground only D...

Страница 4: ...ked position and then pull modules apart Step Two Attach field wiring using the removable terminal block or ZIPLink wiring system WIRE STRIP LENGTH MIN MAX P1 08TD1 UNLOCK LOCK Check all latches are s...

Страница 5: ...Module Configuration Using the Hardware Configuration tool in the Productivity Suite programming software drag and drop the P1 04THM module into the configuration Specify Temperature Scale and Burnou...

Страница 6: ...6 Tech Support 770 844 4200 www productivity1000 com...

Страница 7: ...7 Sales 800 633 0405 www productivity1000 com...

Страница 8: ...failure to follow all applicable codes and standards We do not guarantee the products described in this publication are suitable for your particular application nor do we assume any responsibility fo...

Отзывы: