P1-04RTD Analog Input

The P1-04RTD Input Module provides four differential 

channels  for  receiving  RTD  and  resistance  input 

signals for use with the Productivity1000 system.

RTD Input Specifications . . . . . . . . . . . . . . . . . . . . .  1

General Specifications  . . . . . . . . . . . . . . . . . . . . . .  2

Removable Terminal Block Specifications. . . . . . . .  2

Wiring Diagram and Schematic . . . . . . . . . . . . . . . .  3

Module Installation Procedure . . . . . . . . . . . . . . . . .  4

QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4

Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

Module Configuration  . . . . . . . . . . . . . . . . . . . . . . .  5

Resistance Input Specifications  . . . . . . . . . . . . . . .  6

Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6

Typical Application Example . . . . . . . . . . . . . . . . . .  7

Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

Warranty: Thirty-day money-back guarantee. Two-year limited 

replacement (See www.productivity1000.com for details).

RTD Input Specifications

Inputs Channels

4 Differential

Data Format

Floating Point

Max. Common Mode Voltage

5VDC

Common Mode Rejection

-100dB min. @ DC, -100db min. @ 50/60 Hz*

Absolute Maximum Ratings

Fault Protected Inputs to ±50V

Internal Resolution

16-bit, ±0.1°C or °F

RTD Input Ranges

Pt100 

Pt1000

JPt100

10

 Cu.

25

 Cu.

120

 Ni.              

-200°C/850°C (-328°F/1562°F)

-200°C/595°C (-328°F/1103°F)

-100°C/450°C (-148°F/842°F)

-200°C/260°C (-328°F/500°F)

-200°C/260°C (-328°F/500°F)

-80°C/260°C (-112°F/500°F)

RTD Linearization

Automatic

Excitation Current (all ranges)

210µA

Accuracy vs. Temperature

±10ppm per °C (maximum)

Warm-up Time

2 minutes for ±0.2% repeatability

Maximum Inaccuracy*

±1°C maximum @ 16.7 Hz

±3°C maximum @ 470Hz

±5°C maximum on Cu10 & Cu25

Sample Duration

(Single channel update rate)

Dependent on digital filter settings-

200ms @ 16.7 Hz, 90ms @ 470Hz

Filter Characteristics

Digital Filter cutoff frequencies:

16.7 Hz, 470Hz

All Channel Update Rate

Single channel update rate times the number of 

enabled channels

Open Circuit Detection Time

Burnout detect within 2s

Conversion Method

Sigma-Delta

External DC Power Required

None

*NOTE: Excluding RTD error, including temperature drift

Содержание Productivity 1000 P1-04RTD

Страница 1: ...ejection 100dB min DC 100db min 50 60 Hz Absolute Maximum Ratings Fault Protected Inputs to 50V Internal Resolution 16 bit 0 1 C or F RTD Input Ranges Pt100 Pt1000 JPt100 10 Cu 25 Cu 120 Ni 200 C 850 C 328 F 1562 F 200 C 595 C 328 F 1103 F 100 C 450 C 148 F 842 F 200 C 260 C 328 F 500 F 200 C 260 C 328 F 500 F 80 C 260 C 112 F 500 F RTD Linearization Automatic Excitation Current all ranges 210µA A...

Страница 2: ... 140ºF Storage Temperature 20º to 70ºC 4º to 158ºF Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration IEC60068 2 6 Test Fc Shock IEC60068 2 27 Test Ea Field to Logic Side Isolation 1800VAC applied for 1 second Heat Dissipation 100mW Enclosure Type Open Equipment Module Location Any I O position in a Productivity1000 System Field Wiring Removable terminal block...

Страница 3: ...res to one side of a two wire RTD R COM R 2 wire RTD 3 wire RTD 4 wire RTD Note Leave 4th wire unattached as shown R COM R R COM R R COM R 2 For 2 wire RTD attach a third wire to module common 1 R R and COM wires to an RTD must be equal length and type Refer to RTD manufacturers Notes for maximum accuracy 3 Do not use cable shield as a sensing wire 4 When applicable connect shield to RTD common on...

Страница 4: ...cked position and then pull modules apart Step Two Attach field wiring using the removable terminal block or ZIPLink wiring system LOCK UNLOCK WIRE STRIP LENGTH MIN MAX P1 08TD1 Check all latches are secure after modules are connected QR Code Use any QR Code reader application to display the module s product insert P1 08TD1 P1 08TD1 1 2 3 4 5 6 7 8 9 10 L L L L L L L L 24V 1 2 3 4 0V 5 6 7 8 12 24...

Страница 5: ...Configuration Using the Hardware Configuration tool in the Productivity Suite programming software drag and drop the P1 04RTD module into the base configuration Specify Temperature Scale and Burnout Detection and use the drop down menu to select module range and resolution If desired assign a User Tagname to each output point channel selected and to each Status Bit Item ...

Страница 6: ...solution 0 1 Resolution 0 1 Resolution 0 1 Resolution 0 01 Resolution 0 01 Accuracy vs Temperature 25ppm per C maximum Linearity Error end to end 0 03 16 7 Hz 0 06 470Hz of full scale range maximum at 25 C Monotonic with no missing codes Maximum Inaccuracy 0 10 of full scale range Diagnostics Module Diagnostics Failure 1 bit per module Module Not Ready 1 bit per module Channel Burn out RTD only 1 ...

Страница 7: ... com Typical Application Example Process Variable feedback Heat Controller Heater PID Output Oven Temperature User s Desired Setpoint Resistance Temperature Device to P1 04RTD P1 04RTD R1 R2 R2 COM COM R3 R3 R4 R4 R1 P1 04RTD RTD INPUT Module ...

Страница 8: ...m the failure to follow all applicable codes and standards We do not guarantee the products described in this publication are suitable for your particular application nor do we assume any responsibility for your product design installation or operation If you have any questions concerning the installation or operation of this equipment or if you need additional information please call Technical Su...

Отзывы: