background image

1

Sales 800-633-0405

www.productivity1000.com

24V

V2+
V3+
V4+

0V

COM
COM
COM
COM

V1+

P1-04ADL-2

0-10VDC INPUT

ANALOG

1000

P1-04ADL-2 Analog Input

The P1-04ADL-2 Low Resolution Voltage Analog 

Input Module provides four channels for converting 

0–10 VDC analog signals to digital values of 0–8191 

(13-bit)  for use with the Productivity1000 system.

Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . .  1

General Specifications  . . . . . . . . . . . . . . . . . . . . . .  2

Terminal Block Specifications . . . . . . . . . . . . . . . . .  2

Wiring Diagram and Schematic . . . . . . . . . . . . . . . .  3

Module Installation Procedure . . . . . . . . . . . . . . . . .  4

QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4

Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

Module Configuration  . . . . . . . . . . . . . . . . . . . . . . .  5

Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6

Non-Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . .  6

Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

Warranty: Thirty-day money-back guarantee. Two-year limited 

replacement (See www.productivity1000.com for details).

Terminal Block sold separately, (see wiring options on page 5).

Input Specifications

Input Channels

4

Input Range

0–10 VDC

Signal Resolution

13-bit

Resolution Value of LSB

(least significant bit)

0–10 VDC = 1.22 mV per count

(1LSB = 1 count)

Data Range

0–8191 counts

Input Type

Single-ended (1 common)

Maximum Continuous Overload

±100VDC

Input Impedance

150k

 

Hardware Filter Characteristics

Low Pass, -3dB @ 300Hz

Sample Duration Time

2.5 ms per channel
(does not include ladder scan time)

All Channel Update Rate

10ms

Open Circuit Detection Time

Zero reading within 100ms

Conversion Method

Successive approximation

Accuracy vs. Temperature

±75PPM / ºC maximum

Maximum Inaccuracy

0.5% of range

(including temperature drift)

Linearity Error

±0.036% of range

Monotonic with no missing codes

Input Stability and Repeatability

±0.024% of range

Full Scale Calibration Error

(including offset)

±0.097% of range

Offset Calibration Error

±0.097% of range

Max Crosstalk at DC, 50Hz and 

60Hz

±0.049% of range

External Power Supply Required

24VDC (-20% / + 25%), 30mA

Содержание Productivity 1000 P1-04ADL-2

Страница 1: ...5 Input Specifications Input Channels 4 Input Range 0 10 VDC Signal Resolution 13 bit Resolution Value of LSB least significant bit 0 10 VDC 1 22 mV per count 1LSB 1 count Data Range 0 8191 counts In...

Страница 2: ...C 4 to 158 F Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration IEC60068 2 6 Test Fc Shock IEC60068 2 27 Test Ea Field to Logic Side Isolation 1800VAC applied for...

Страница 3: ...IRCUIT POWER ISOLATED ANALOG CIRCUIT COMMON INTERNAL MODULE CIRCUITRY 24V COM COM P1 04ADL 2 Wiring Diagram 24 VDC User Supplied Power Voltage Input Circuits 3 Wire Voltage Transmitter V COM 3 Wire Tr...

Страница 4: ...ked position and then pull modules apart Step Two Attach field wiring using the removable terminal block or ZIPLink wiring system LOCK UNLOCK WIRE STRIP LENGTH MIN MAX P1 08TD1 Check all latches are s...

Страница 5: ...nal Block only P1 10RTB Quantity 1 4 Spring Clamp Terminal Block only P1 10RTB 1 Quantity 1 5 Accessories ZL RTB COM TW SD SL 1 TW SD MSL 1 ZL RTB20 ZL RTB20 1 2 1 Cable ZIPLink Module Complete System...

Страница 6: ...in max The Scale Linear function can be used to Convert an application specific range to range which is native to the analog output module Make other linear conversions in ranges appropriate to the ap...

Страница 7: ...7 Sales 800 633 0405 www productivity1000 com...

Страница 8: ...he failure to follow all applicable codes and standards We do not guarantee the products described in this publication are suitable for your particular application nor do we assume any responsibility...

Отзывы: