1
Sales 800-633-0405
www.productivity1000.com
COM
COM
COM
COM
24V
I2+
I3+
I4+
0V
I1+
P1-04ADL-1
0-20mA INPUT
ANALOG
1000
P1-04ADL-1 Analog Input
The P1-04ADL-1 Low Resolution Analog Input
Module provides four current sinking channels for
converting 0–20 mA analog signals to a digital value
of 0–8191 (13-bit) for use with the Productivity1000
system.
Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 1
General Specifications . . . . . . . . . . . . . . . . . . . . . . 2
Terminal Block Specifications . . . . . . . . . . . . . . . . . 2
Wiring Diagram and Schematic . . . . . . . . . . . . . . . . 3
Module Installation Procedure . . . . . . . . . . . . . . . . . 4
QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . 5
Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Non-Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . 6
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Warranty: Thirty-day money-back guarantee. Two-year limited
replacement (See www.productivity1000.com for details).
Terminal Block sold separately, (see wiring options on page 5).
Input Specifications
Input Channels
4
Module Signal Input Range
0–20 mA
Signal Resolution
13-bit
Resolution Value of LSB
(least significant bit)
0–20 mA = 2.44 µA per count
(1LSB = 1 count)
Data Range
0–8191 counts
Input Type
Sinking, Single-ended (1 common)
Maximum Continuous Overload
±31mA
Input Impedance
247
Ω
, ±0.5%, 1/4W Current Input
Filter Characteristics
Low Pass, -3dB @ 120Hz
Sample Duration Time
2.5 ms per channel
(does not include ladder scan time)
All Channel Update Rate
10ms
Open Circuit Detection Time
Zero reading within 100ms
Conversion Method
Successive approximation
Accuracy vs. Temperature
±75PPM / ºC maximum
Maximum Inaccuracy
0.5% of range
(including temperature drift)
Linearity Error (end to end)
±0.037% of range
Monotonic with no missing codes
Input Stability and Repeatability
±0.024% of range
Maximum Full Scale Calibration
Error
±0.098% of range
Offset Calibration Error
±0.098% of range
Maximum Crosstalk at DC,
50Hz and 60Hz
±0.049% of range
Recommended Fuse (external)
Edison S500-32-R, 0.032 A fuse
External Power Supply Required
24VDC (-20% / + 25%), 30mA