Introduction – How To Get Started
Automationdirect.com would like to thank you for your purchase of the Durapulse GS10 AC drive. The GS10
drive is a state-of-the-art, full-featured AC drive. The Quick-Start Guide below will introduce you to many of
the GS10 drive features and help you configure the GS10 drive in a minimum amount of time.
Emergency Stop
The GS10 drive offers a standard Emergency Stop circuit.
Please see the Control-Circuit Wiring diagrams and Safety wiring (
) for how to wire the multifunction
input as the Emergency Stop.
After wiring the drive (
but before applying power
), test the system by pressing the E-stop button (or otherwise
break the safety circuit) and verify that the E-stop digital input is triggered. When the E-stop is active, EF1 will
display on the drive LED and the drive will not run.
Powering Up the GS10 Drive
Apply AC line power to the GS10 drive, but don’t engage the safety circuit yet (keep the E-stop PB pushed in).
Starting, Stopping, and Controlling the Speed of the GS10 Drive
Out of the box GS10 drives are set to use the keypad buttons to RUN and STOP the drive and vary the drive
speed. The drive can also be configured to run from potentiometers, external pushbuttons, etc.
Do not attempt to run the motor yet. Certain parameters (especially the motor protection parameters) must
be set first.
Configure the Drive
The tables below list those parameters typically used in most applications. You can navigate to any of these
parameters through the keypad. (Refer to
for information and instructions for using the Digital
Keypad.) Before configuring the drive, reset the drive to defaults. Set P00.02=9 (50Hz) or 10 (60Hz). Then cycle
power to the drive.
All applications need to configure the parameters in the “Quick Configuration” table. At minimum, you MUST
configure these motor parameters before operating the drive:
• 01.02 Motor1 Max Output Voltage (this will typically be either 230V or 460V)
• 05.01 Motor1 Rated Amps (depends on the motor)
• 01.01 Motor1 Max Output Frequency (this will typically be 50Hz or 60Hz)
The main configuration parameters required to get your drive up and running are included in this guide.
For more advanced configuration options, please see the User Manual. Your application will dictate which
parameters need to be configured. It is NOT necessary to configure every parameter listed in the tables in the
User Manual, use only those you need.
Parameter Groups
Group Number
Group Category
00
Drive Config
01
Basic Config
02
Digital I/O Config
03
Analog I/O Config
04
Multi-Step Speed Config
05
Motor Config
06
Protection Config
07
Special Parameters
08
PID Config
09
Communications Config
10
Speed Control Config
11
Advanced Config
12
Function
13
Macro Config
14
Protection (2) Config
After configuring the minimum settings, you can now engage the safety circuit. The RUN and STOP/RESET
buttons should Start and Stop the drive. To adjust the output frequency, press the MENU button until the
frequency screen appears. Use the Up and Down arrow buttons to adjust the frequency, the press ENTER to
confirm. Press ENTER again to return to the main menu.
Parameter Set Up
DURA
pulse
GS10 AC Drives offer parameter setup from the keypad for some of the most common drive
applications. Choose parameters from the table below, then set the applicable parameters for that
application as shown.
To Configure Parameters:
From the power up screen:
1) Press
MENU
until you see
H 0.00
(this is the actual drive frequency) and press
ENTER
.
2) Use the
UP/DWN
arrows to select the parameter group you want and press
ENTER
.
3) Use the
UP/DWN
arrows to select the parameter number you want within that group and press
ENTER
.
4) Change the value of the parameter using the
UP/DWN
arrows and press
ENTER
.
5) Press
MENU
to exit back to the main menu.
6) Repeat as needed until all required parameters are configured.
Please refer to the user manual if you need more detailed information about the
parameters.
DURA
pulse
GS10 Parameter Settings – Quick Configuration*
Parameter
Description
Range
Default
User
Group
#
00 00
GS10 Model ID
Read Only
n/a
00 01
Displays AC drive rated current
Displays value based on model
n/a
00 02
Restore to default**
0=No function
1=Parameter write protect
5=Reset kWH display to 0
8=Keypad disable
9=Reset 50Hz defaults
10=Reset 60Hz defaults
11=Reset 50Hz defaults (keep user config)
12=Reset 60Hz defaults (keep user config)
0
00 06
Firmware Version
Read Only
n/a
00 11
Speed Control Mode
0
=
VF (IM V/F control)
2
=
SVC (Parameter 05.33 set as IM or PM)
0
00 16
Load Selection
0
=
VT (Variable Torque)
1
=
CT (Constant Torque)
1
00 20
Frequency Command Source (Auto)
0=Digital keypad
1=Communication RS-485 input
2=External analog input (refer to parm 03.00)
3=External UP/DOWN terminal
4=Pulse input without direction command
(refer to parm 10.16 without direction)
7=Digital keypad dial
0
00 21
Operation Command Source (Auto)
0=Digital keypad
1=External terminals
2=Communication RS-485 input
0
00 22
Stop Method
0=Ramp to stop
1=Coast to stop
2=Stop by simple positioning
0
00 23
Motor Direction Control
0=Enable forward/reverse
1=Disable reverse
2=Disable forward
0
01 00
Motor 1 Max Frequency
0.00-599.0 Hz
60
01 01
Motor 1 Base Frequency
0.00-599.0 Hz
60
01 02
Motor 1 Rated Voltage
110V/230V: 0.0~255.0
460V: 0.0~510.0V
220.0
440.0
01 09
Startup Frequency
0.00-599.0 Hz
0.5
01 10
Output Frequency Upper Limit
0.00-599.0 Hz
599.0
01 11
Output Frequency Lower Limit
0.00-599.0 Hz
0.00
01 12
Acceleration Time 1
P01.45=0: 0.00-600.0 sec
P01.45=1: 0.00-6000 sec
10.00
10.00
01 13
Deceleration Time 1
P01.45=0: 0.00-600.0 sec
P01.45=1: 0.00-6000 sec
10.00
10.00
01 20
Jog Acceleration Time
P01.45=0: 0.00-600.0 sec
P01.45=1: 0.00-6000 sec
10.00
10.00
01 21
Jog Deceleration Time
P01.45=0: 0.00-600.0 sec
P01.45=1: 0.00-6000 sec
10.00
10.00
01 22
Jog Frequency
0.00-599.0 Hz
6.00
* Assumes default V/Hz mode with no feedback. To change control modes see complete parameter listing in User manual.
** Reboot drive after resetting defaults.
Note:
Drive default is Auto mode and cannot be changed from the keypad. For Local/Hand, use Discrete input configuration
settings (P02.00–P02.05) and P00.29–P00.31.
(table continued next column)
DURA
pulse
GS10 Parameter Settings – Quick Configuration (continued)
Parameter
Description
Range
Default
User
02 00
2-wire / 3-wire Control
0=No function
1=2-wire mode 1, power on for operation
control (M1: FWD/STOP, M2: REV/STOP)
2=2-wire mode 2, power on for operation
control (M1: RUN/STOP, M2 REV/FWD)
3=3-wire, power on for operation control
(M1: RUN, M2: REV/FWD, M3: STOP)
4=2-wire mode 1, fast start up
(M1: FWD/STOP, M2: REV/STOP)
5=2-wire mode 2, fast start up
(M1: RUN/STOP, M2: REV/FWD)
6=3-wire, fast start up
(M1: RUN, M2: REV/FWD, M3: STOP)
Note:
In fast start up mode, the drive skips
detecting IGBT signal and will run
immediately. When using fast start up mode:
• Terminal output stays in ready status and
drive responds to commands immediately.
• The output terminal will have higher
voltage
• If the drive is short circuited an OC error
will display when running up
1
02 01
Multi-function Input Command 1
(FWD/DI1)
See “Multi-function Input Selections” on
0
02 02
Multi-function Input Command 2
(REV/DI2)
0
02 03
Multi-function Input Command 3 (DI3)
1
02 04
Multi-function Input Command 4 (DI4)
2
02 05
Multi-function Input Command 5 (DI5)
3
02 13
Multi-function Output 1 (R1)
See “Multi-function Output Selections” on
11
02 16
Multi-function Output 2 (DO1)
0
02 35
Auto-run on Power up (includes after
a Fault reset)
0: Disable
1: Drive Runs if Cmd ON after Flt Reset or
Pwr up
0
03 00
Analog Input Selection (AI)
See “AI Multi-function Input Selections” on
1
03 20
Multi-function Output (AO1)
See “AO1 Multi-function Output Selections”
0
03 28
AI terminal input selection
0=0-10 V
1=0-20 mA
2=4-20 mA
0
04
00
to
14
Multi-step Speed Frequency 1–15
0.00-599.0 Hz
0.00
05 00
Motor Parameter Auto-tuning
(use with P00.11=2)
0=No function
1=Dynamic test for induction motor (IM)
2=Static test for induction motor (IM)
5=PM Rotary tuning
13=PM Static tuning
0
05 01
Motor 1 Full Load Amps (FLA)
10-120% of drive rated current
#.##
05 03
Motor 1 Rated RPM
0-65535
1710
05 04
Motor 1 Number of poles
2-20
4
06 06
Over-torque Detection Selection
(Motor 1)
0=No function
1=Continue operation after over-torque
detection during constant speed operation
2=Stop after over-torque detection during
constant speed operation
3=Continue operation after over-torque
detection during RUN
4=Stop after over-torque detection during
RUN
0
06 07
Over-torque Detection Level (Motor 1)
10–250%
(100% corresponds to the rated current of
the drive)
120
06 08
Over-torque Detection Time (Motor 1) 0.1–60.0 seconds
0.1
06 13
Motor 1 Electronic Thermal Overload
Relay
0=Inverter motor (with external forced
cooling)
1=Standard motor (motor with fan on the
shaft)
2=Disabled
Note:
A value of 0 or 1 is recommended to
protect the motor in most applications.
2
06 14
Motor 1 Electronic Thermal Relay Time 30.0-600.0
60
06 55
Drive Derating Method
0=Constant rated current and limit carrier
wave by load current and temperature
1=Constant carrier frequency and limit load
current by setting carrier wave
2=Constant rated current (same as setting 0)
but close current limit
0
07 10
Restart after fault action
0=Stop operation
1=Speed tracking by current speed
2=Speed tracking by minimum output
frequency
0
(table continued next page)