ACT/ACTR SERIES

INSTALLATION

INSTRUCTIONS

Quick Start Guide

1. Run the wire to be monitored through

the aperture.

2. Mount the sensor to a surface, if

needed.

3. Connect output wiring.

A. Use up to 14 AWG copper

wires.

B. 10 VDC models: make sure

output load is at least 1 Mq.

C. 4-20 mA models: make sure

loop voltage is correct

4. Select Range. Choose correct range

by positioning the Range Jumper
(750/2000 series have a 3-position
switch rather than a jumper).

Ranges & Maximum Amps - Input Maximums

MAXIMUM INPUT AMPS

MODEL

RANGE

CONTINUOUS

MAXIMUM
6 Seconds

MAXIMUM
1 Second

ACT005
and
ACTR005

0 - 2 A

80 A

125 A

250 A

0 - 5 A

100 A

125 A

250 A

ACT050

and

ACTR050

0 - 10 A

80 A

125 A

250 A

0 - 20 A

110 A

150 A

300 A

0 - 50 A

175 A

215 A

400 A

ACT200
and
ACTR200

0 - 100 A

200 A

300 A

600 A

0 - 150 A

300 A

450 A

800 A

0 - 200 A

400 A

500 A

1000 A

ACT750
and
ACTR750

0 - 375 A

750 A

1500 A

3750 A

0 - 500 A

750 A

1500 A

3750 A

0 - 750 A

750 A

1500 A

3750 A

ACT2000
and
ACTR2000

0 - 1000 A 2000A

4000 A

10000 A

0 - 1333 A 2000A

4000 A

10000 A

0 - 2000 A 2000A

4000 A

10000 A

e

r

o

C

d

e

x

i

F

-

F

e

r

o

C

-t

il

p

S

-

S

)

h

c

ti

w

S

e

t

a

t

S

d

il

o

S

(

A C T 005 - 42L - F

SENSOR TYPE:

T - Transducer, Average responding sinusoidal waveforms

TR - Transducer, True RMS, non sinusoidal waveforms

 

4 -20 mA output only

AC current operated

FULL SCALE RANGE:

005 - 2 A and 5 A

050 - 10, 20, 50 A

200 - 100, 150, 200 A

750 - 375, 500, 750 A

2000 - 1000, 1333, 2000A

0 - 10 to 10 VDC, self-powered       

42L - 4 to 20 mA loop powered out

(requires 24 VDC power supply)

OUTPUT

CASE STYLE

Specifications

Output Signal

0-10 VDC or 4-20 mA (see Part Number Key)

Output Limit

ACTx-010

15 VDC

ACTx-42L

Units up to 200 A: 32 mA
Units from 200 A up to 2000 A: 23 mA

ACTRx-42L

23 mA

Frequency Range

ACTx-010

50-60 Hz (Sinusoidal)

ACTx-42L

20-100 Hz (Sinusoidal)

ACTRx-42L

10-400 Hz (All Wave forms)

Response Time To 90% of Step Change

ACTx-010

100 ms

ACTx-42L

Units up to 200 A: 300 ms
Units from 200 A up to 2000 A: 500 ms

ACTRx-42L

600 ms

Accuracy

ACTx-010

1% FS

ACTx-42L

1% FS

ACTRx-42L

1% FS

General

Power Supply,

-42L

24 VDC Nominal, 40 VDC Max.

Output Load,

-010

1 M

recommended, 100 K

: add 1.3% error

Isolation Voltage

To 200 A: UL listed to 1270 VAC, Tested to 5kV
Units 750 and 2000 A: 600 VAC

Case

UL 94V-0 Flammability rated thermoplastic

Environmental

-4 to 122°F (-20 to 50° C) operating temperature

0-95% RH, non-condensing humidity

Listings

UL 508 and cUL Listed, UL File E222847
CE Certified

ACT/R-v-mu-Inst - Rev 4 0311

PN 291002129