Part Number Key
AutomationDirect.com (ADC)
3505 Hutchinson Road, Cumming, GA 30040
Phone: (800) 633-0405 or (770) 889-2858
Fax: (770) 889-7876
ACT/ACTR SERIES
INSTALLATION
INSTRUCTIONS
Quick Start Guide
1. Run the wire to be monitored through
the aperture.
2. Mount the sensor to a surface, if
needed.
3. Connect output wiring.
A. Use up to 14 AWG copper
wires.
B. 10 VDC models: make sure
output load is at least 1 Mq.
C. 4-20 mA models: make sure
loop voltage is correct
4. Select Range. Choose correct range
by positioning the Range Jumper
(750/2000 series have a 3-position
switch rather than a jumper).
Ranges & Maximum Amps - Input Maximums
MAXIMUM INPUT AMPS
MODEL
RANGE
CONTINUOUS
MAXIMUM
6 Seconds
MAXIMUM
1 Second
ACT005
and
ACTR005
0 - 2 A
80 A
125 A
250 A
0 - 5 A
100 A
125 A
250 A
ACT050
and
ACTR050
0 - 10 A
80 A
125 A
250 A
0 - 20 A
110 A
150 A
300 A
0 - 50 A
175 A
215 A
400 A
ACT200
and
ACTR200
0 - 100 A
200 A
300 A
600 A
0 - 150 A
300 A
450 A
800 A
0 - 200 A
400 A
500 A
1000 A
ACT750
and
ACTR750
0 - 375 A
750 A
1500 A
3750 A
0 - 500 A
750 A
1500 A
3750 A
0 - 750 A
750 A
1500 A
3750 A
ACT2000
and
ACTR2000
0 - 1000 A 2000A
4000 A
10000 A
0 - 1333 A 2000A
4000 A
10000 A
0 - 2000 A 2000A
4000 A
10000 A
e
r
o
C
d
e
x
i
F
-
F
e
r
o
C
-t
il
p
S
-
S
)
h
c
ti
w
S
e
t
a
t
S
d
il
o
S
(
A C T 005 - 42L - F
SENSOR TYPE:
T - Transducer, Average responding sinusoidal waveforms
TR - Transducer, True RMS, non sinusoidal waveforms
4 -20 mA output only
AC current operated
FULL SCALE RANGE:
005 - 2 A and 5 A
050 - 10, 20, 50 A
200 - 100, 150, 200 A
750 - 375, 500, 750 A
2000 - 1000, 1333, 2000A
0 - 10 to 10 VDC, self-powered
42L - 4 to 20 mA loop powered out
(requires 24 VDC power supply)
OUTPUT
CASE STYLE
Specifications
Output Signal
0-10 VDC or 4-20 mA (see Part Number Key)
Output Limit
ACTx-010
15 VDC
ACTx-42L
Units up to 200 A: 32 mA
Units from 200 A up to 2000 A: 23 mA
ACTRx-42L
23 mA
Frequency Range
ACTx-010
50-60 Hz (Sinusoidal)
ACTx-42L
20-100 Hz (Sinusoidal)
ACTRx-42L
10-400 Hz (All Wave forms)
Response Time To 90% of Step Change
ACTx-010
100 ms
ACTx-42L
Units up to 200 A: 300 ms
Units from 200 A up to 2000 A: 500 ms
ACTRx-42L
600 ms
Accuracy
ACTx-010
1% FS
ACTx-42L
1% FS
ACTRx-42L
1% FS
General
Power Supply,
-42L
24 VDC Nominal, 40 VDC Max.
Output Load,
-010
1 M
⏲
recommended, 100 K
⏲
: add 1.3% error
Isolation Voltage
To 200 A: UL listed to 1270 VAC, Tested to 5kV
Units 750 and 2000 A: 600 VAC
Case
UL 94V-0 Flammability rated thermoplastic
Environmental
-4 to 122°F (-20 to 50° C) operating temperature
0-95% RH, non-condensing humidity
Listings
UL 508 and cUL Listed, UL File E222847
CE Certified
ACT/R-v-mu-Inst - Rev 4 0311
PN 291002129