Appendix D: Data Logging Address Notation
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Productivity Series PLCs
Reading Coils (Function Code 1)
Function Code SiteLink Modbus Address
Data Type
Productivity Address*
1
0
BOOL
000001
1
1
000002
1
65534
065535
* Modbus addresses must be assigned to the tags in the “Tag Database” area of the Productivity Suite Programming
Software.
Reading Input Bits (Function Code 2)
Function Code SiteLink Modbus Address
Data Type
Productivity Address*
2
0
BOOL
100001
2
1
100002
2
65534
165535
* Modbus addresses must be assigned to the tags in the “Tag Database” area of the Productivity Suite Programming
Software.
Reading Input Registers (Function Code 4)
Function Code SiteLink Modbus Address
Data Type
Productivity Address**
4
0
INT16, UINT16 or
BOOL*
300001
4
1
300002
4
65534
365535
4
0
INT32 or UINT32
300001/300002
4
1
300002/300003
4
65534
365535/365536
4
0
FLOAT32
300001/300002
4
1
300002/300003
4
65534
365535/365536
* BOOL: When using BOOL with Input and Holding Registers, a zero value in the register indicates False in the data logger.
Any non-zero value indicates True in the data logger.
** Modbus addresses must be assigned to the tags in the “Tag Database” area of the Productivity Suite Programming
Software.
Содержание STRIDE SiteLink SE-SL3011
Страница 1: ...Manual Number SE SLVPN USER M Industrial VPN Router USER MANUAL SiteLink Series...
Страница 2: ......
Страница 6: ......
Страница 8: ......
Страница 14: ...Table of Contents STRIDE SiteLink Series Industrial VPN Routers User Manual 1st Edition vi...
Страница 123: ......