Chapter 1:  Getting Started

Page 1–3

S

tride

®

 MB Gateway User Manual

 – 

1st Edition Rev. E – August 2020

Introduction

Modbus is one of the most popular communication protocols in the automation industry because 

it supports both traditional RS-232/422/485 devices and industrial Ethernet devices. Many 

industrial devices, such as PLCs, HMIs, instruments and meters use Modbus as their standard 

communication protocol. However, the Modbus protocols running over serial and Ethernet are so 

different that a communication gateway is needed as a bridge for integrating devices from these 

two networks. The 

STRIDE

® Modbus Gateway provides that bridge between Modbus RTU (Serial) 

products and Modbus TCP (Ethernet) products.

The gateway converts bidirectionally between Modbus RTU or Modbus ASCII protocols and 

Modbus TCP. In addition to its compact size, the gateway features up to two 10/100 Mbps Ethernet 

ports and up to four RS232/422/485 serial ports.

SECURITY NOTE: When implementing any method of remote access to your equipment, you 

need to consider the security exposure in order to minimize the risks to your processes and 

your equipment. Security should always be carefully evaluated for each installation. Refer to 

“Appendix D: Security Considerations for Control Systems Networks” for more information.

.

Product Overview

Key features include:

 

9

Industrial 1, 2, or 4 serial port,  and 1 or 2 Ethernet port Modbus Gateways  

(Modbus RTU/ASCII <-> ModbusTCP)

 

9

Automatic read function “Agent Mode”

 

9

Ethernet ports each support up to 16 TCP devices, client or server

 

9

Serial ports each support up to 128 slave devices or 1 master device

 

9

DIP switch selectable termination resistor for RS-485 mode 

 

9

High Serial Isolation Voltage (2kV)

 

9

UL61010 with Class 1 Division 2 hazardous location rating

 

9

Metal housing with wide temperature rating (−40 to +75°C)

Hardware

STRIDE

 Modbus Gateway Models

Part Number

Ethernet Ports 

RJ45, 10/100Mbps

Serial Ports 

D-sub 9 pin

SGW-MB1511-T

1

1

SGW-MB1512-T

1

2

SGW-MB1524-T

2

4

Ethernet Interface

Port

Shielded RJ45

Speed

10/100 Mbps

Protection

Built-in 1�5 kV magnetic isolation

Protocol Supported

Modbus TCP/IP client and server

Modbus TCP devices supported

16 simultaneous Modbus TCP connections per Ethernet port

Cable Type

Autodetects Ethernet cable types (MDI/MDIX)

Default IP address

192�168�0�249 

192�168�1�249 (Ethernet Port 2, SGW-MB1524-T)

Содержание STRIDE SGW-MB1511-T

Страница 1: ...This Chapter User Manual Overview 1 2 Introduction 1 3 Product Overview 1 3 Hardware 1 3 Hardware Reset Button 1 5 DIP Switches 1 5 LEDs 1 5 Installation DIN Rail Mounting 1 6 Dimensional Drawings 1 7...

Страница 2: ...you cannot find the solution to your particular application or if for any reason you need additional technical assistance please call technical support at 770 844 4200 We are available weekdays from 9...

Страница 3: ...sks to your processes and your equipment Security should always be carefully evaluated for each installation Refer to Appendix D Security Considerations for Control Systems Networks for more informati...

Страница 4: ...Input Redundant input terminals Input Voltage 12 24 48 VDC Max Input Voltage Range 9 6 60 VDC Appliance Class Class III SELV power source Reverse Power Protection Yes Overload Protection Yes Environm...

Страница 5: ...is one yellow SPEED LED for each Ethernet port LED ON indicates Ethernet speed is 100 Mbps LED OFF indicates Ethernet speed is 10 Mbps Link Activity RJ45 Green There is one green Link Activity LED for...

Страница 6: ...nt when installed in Class 1 Division 2 Hazardous Locations The gateway can be snapped onto a standard 35mm x 7 5 mm height DIN rail Standard CENELEC EN50022 and can be mounted either vertically or ho...

Страница 7: ...mensional Drawings NOTE Allow 20mm 0 79 clearance around each gateway for proper cooling Dimensions Part No Weight Width A Depth B Height C mm inches SGW MB1511 T 0 17 kg 0 36 lb 30 0 1 18 68 0 2 68 1...

Страница 8: ...A recommended DC power supply is AutomationDirect com part number PSL 24 010 Terminal block connector is Degson 2EDGK 5 08 04P 14 1000AH or equivalent Ferrule required for stranded wire Wire Size Ran...

Страница 9: ...und loops the cable shield should be tied to the metal connector body at one end of the cable only Electrical isolation is also provided on the Ethernet ports for increased reliability Ethernet Cable...

Страница 10: ...ns a DIP switch selectable 120 Termination Resistor between RXD and RXD for each serial port when the Gateway is wired at one end of the serial network NC RS 422 RS 485 Gateway Slave 1 Slave 2 Last Sl...

Страница 11: ...d store that data into gateway shared memory If a Modbus query comes in for one of those data points the gateway will immediately respond with the data it has stored and thereby respond much faster th...

Страница 12: ...Chapter 1 Getting Started Page 1 12 Stride MB Gateway User Manual 1st Edition Rev E August 2020...

Отзывы: