Page 3–22
Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 3: Configuration and Parameters
“a
dvanCed
” m
enu
of
p
arameTers
P1.0 –
Save Parameters
Hold. Reg. Type:
Description:
Read/Write
Saves all Read/Write parameters to non-volatile memory.
Note: This does not save the parameters to an external USB drive.
Range:
Modbus Decimal Value: Default (decimal):
• No : Parameters remain unchanged.
• Yes : Parameters are written.
• 0
• 1
• No (0)
Modbus Address:
Modbus Format:
Touchscreen Menu Path:
a
dvanCed
“a
uTomaTiC
s
eTTings
” p
arameTers
P2.0 –
Automatic Pedestal
Hold. Reg. Type:
Description:
Read/Write
Automatically controls the starting torque by adjusting the start voltage.
Range:
Modbus Decimal Value: Default (decimal):
• Off : The initial torque is defined by the “Start Pedestal.”
• On : The initial torque is increased until the motor starts to
rotate at a moderate speed.
• 0
• 1
• Off (0)
Modbus Address:
Modbus Format:
19840 ( 4D80 hex )
16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Automatic Settings → Automatic Pedestal
P2.1 –
Automatic Ramp
Hold. Reg. Type:
Description:
Read/Write
Automatically controls the torque applied to the motor during the soft start by automatically
adjusting “Start Time” and “Current Limit.”
Range:
Modbus Decimal Value: Default (decimal):
• Off : The ramp time depends on the “Start Time” and “Current
Limit.”
• On : The torque is adjusted to suit the load.
• 0
• 1
• Off (0)
Modbus Address:
Modbus Format:
20352 ( 4F80 hex )
16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Automatic Settings → Automatic Ramp
P2.2 –
Automatic End Start (1)
Hold. Reg. Type:
Description:
Read/Write
Automatically controls the time taken for the motor to start.
Range:
Modbus Decimal Value: Default (decimal):
• Off : The ramp time depends on the “Start Time” and “Current
Limit.”
• On : The ramp time is shortened if the motor is at speed before
the end of the “Start Time.”
• 0
• 1
• Off (0)
Modbus Address:
Modbus Format:
19968 ( 4E00 hex )
16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Automatic Settings → Automatic End Start (1)
Содержание Stellar SR55 Series
Страница 1: ...Stellar SR55 Soft Starter User Manual SR55_UMW First Edition Revision F...
Страница 2: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Страница 6: ...Page W 4 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Страница 8: ...Page H 2 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Страница 14: ...TOC 6 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 Table of Contents BLANK PAGE...
Страница 148: ...Page 5 22 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 Chapter 5 Communications BLANK PAGE...
Страница 166: ...Page 6 18 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 Chapter 6 Accessories BLANK PAGE...
Страница 172: ...Page A 6 Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 Appendix A Updating Firmware BLANK PAGE...
Страница 201: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019 BLANK PAGE...
Страница 202: ...Stellar SR55 Series Soft Starter User Manual 1st Ed Rev F 09 18 2019...