SR35 Quick-Start Guide

Stellar® SR35 Series Soft Starter Quick Start Guide – 1st Ed – 07/09/2020

s

HorT

 C

IrCuIT

 p

roTeCTIon

Short Circuit Protection – SR35 Frame Size 1

Type designation (SR35-)

017

022

027

034

041

052

065-6

Rated operational 

current

I

e

A

17

22

29

35

41

55

66

Rated conditional 

short circuit 

current

I

q

kA

5

5

5

5

5

5

10

Class J time-delay 

fuse #1

Maximum 

rating Z

1

A

30

40

50

60

70

100

125

UL Listed inverse-

time delay circuit 

breaker #1

Maximum 

rating Z

2

A

60

60

60

60

60

150

150

Semiconductor 

fuse (class aR) 

#2

 

Type

Mersen 6,9 URD 30__ 

Bussmann 170M30__ 

Bussmann 170M31__ 

Bussmann 170M32__ 

SIBA 20 61__

Mersen 6,9 URD 31__ 

Bussmann 170M40__ 

Bussmann 170M41__ 

Bussmann 170M42__ 

SIBA 20 61__

Rating

A

160

160

200

200

250

250

250

Short Circuit Protection – SR35 Frame Sizes 2 & 3

Type designation (SR35-)

077

100

125

156

192

242

302

361

Rated operational 

current

I

e

A

80

106

132

160

195

242

302

361

Rated conditional 

short circuit 

current

I

q

kA

10

10

10

10

10

18

18

18

Class J time-delay 

fuse #1

Maximum 

rating Z

1

A

150

200

250

300

400

450

600

600

UL Listed inverse-

time delay circuit 

breaker #1

Maximum 

rating Z

2

A

250

300

350

450

500

700

800

800

Semiconductor 

fuse (class aR) 

#2

 

Type

Mersen 6,9 URD 31__ 

Bussmann 170M40__ 

Bussmann 170M41__ 

Bussmann 170M42__ 

SIBA 20 61__

Mersen 6,9 URD 33__ 

Bussmann 170M60__ 

Bussmann 170M61__ 

Bussmann 170M62__ 

SIBA 20 63__

Rating

A

400

400

550

550

550

800

900

1000

# 1.   Suitable For Use On A Circuit Capable Of Delivering Not More Than ___I

q

___ rms Symmetrical 

Amperes, 600Volts Maximum, When Protected by Class J time delay Fuses with a Maximum Rating 

of ___Z

1

___ or by a Circuit Breaker with a Maximum Rating of ___Z

2

___.

# 2.   Correctly selected semiconductor fuses can provide additional protection against damage to the 

SR35 unit (this is sometimes referred to as type 2 co-ordination).  These semiconductor fuses are 

recommended to provide this increased protection.

Содержание Stellar SR35 Series

Страница 1: ...Stellar SR35 Soft Starter Quick Start Guide...

Страница 2: ...ower Circuit Wiring Diagram 3 phase 10 Single Phase Operation 11 Power Circuit Wiring Diagram 1 phase 11 Control Terminal Connections 12 Control Terminal Functions 12 3 Wire Control Circuit Wiring Dia...

Страница 3: ...his symbol should be obeyed to avoid possible damage to the equipment and personal injury or death Protective Earth Ground Indicates a terminal which is intended for connection to an external conducto...

Страница 4: ...hen installing the SR35 soft starter into a cabinet ventilation must be provided if the heat output of the unit is greater than the cabinet can dissipate The heat dissipated can be approximated with t...

Страница 5: ...is clear of all personnel and property Failure to follow this practice may result in death serious injury or damage to equipment Accessories The following accessories have been developed and tested fo...

Страница 6: ...17 to SR35 065 Dimensions mm in 148 5 83 108 4 25 90 3 54 165 6 50 181 7 13 Weight 1 97kg 3 75lb Note SR35 soft starters may be horizontally mounted with deration See Horizontal Mounting Rating Tables...

Страница 7: ...077 to SR35 192 Dimensions mm in 237 9 3 147 5 8 75 3 0 283 11 1 296 11 7 Weight 6 kg 13 22lb Note SR35 soft starters may be horizontally mounted with deration See Horizontal Mounting Rating Tables Cl...

Страница 8: ...35 361 Dimensions mm in 205 8 1 160 6 3 60 2 4 435 17 1 490 19 3 162 9 6 4 332 13 1 Weight 15kg 33 10lb Note SR35 soft starters may be horizontally mounted with deration See Horizontal Mounting Rating...

Страница 9: ...d as an option for short circuit protection of the semiconductors These fuses must be fitted externally to the SR35 chassis to comply with certain standards It is the responsibility of the installer a...

Страница 10: ...uide 1st Ed 07 09 2020 Electrical Connections 3 Phase Electrical Supply Connections L1 L2 L3 RJ45 connector Modbus RTU USB Connector Control Terminals AC Induction Motor Connections T1 T2 T3 Power Cir...

Страница 11: ...The base rating of the unit is unchanged Power Circuit Wiring Diagram 1 phase NOTE Refer to the SR35 single phase AC motor connectivity insert for additional single phase motor wiring details 2 T1 4 T...

Страница 12: ...C Specification See General Specifications on page 18 for VA rating residual ripple 100mV spikes switching peaks 240mV Turn On Off response no overshoot of Vout Overvoltage voltage protection output v...

Страница 13: ...gram K1 0V Start Stop 24V D1 D2 13 0V COM 14 21 22 FU1 24V dc NOTE 110 230V control supply possible with optional control supply module SR35 PSU 2 Wire Control Circuit Wiring Diagram 2 Wire Control Wi...

Страница 14: ...erload trip settings are determined by the Motor Current setting and the Trip Class setting Trip class choices are Class 10 Class 20 and Class 30 The SR35 soft starters are protected using full I2T mo...

Страница 15: ...3 Control scheme Local Control Terminal Modbus RTU 4 Keypad guidance wizard Displays which keys are valid for specific menu items 5 Motor overload level 0 to 100 6 Control keypad 7 Status LED incorpor...

Страница 16: ...Stellar SR35 Series Soft Starter Quick Start Guide 1st Ed 07 09 2020 How to Configure the SR35 Operation Local Motor Start Example Navigation Method Auto Application Setup Center button to adjust Quic...

Страница 17: ...ded 10 10 7 10 3 5 30 Crusher 40 10 0 30 3 5 60 Fan High Inertia 40 10 0 30 3 5 60 Fan Low Inertia 30 15 0 10 3 5 30 Grinder 40 10 0 20 3 5 40 Mill 40 10 0 20 3 5 40 Mixer 10 10 0 20 4 25 Moulding M C...

Страница 18: ...ors connected between motor windings and supply Number of poles 3 main poles 2 main poles controlled by semiconductor switching element Rated insulation voltage Ui Main circuit See Key to part numbers...

Страница 19: ...contact normally closed 21 22 Utilisation category voltage rating current rating Resistive load 250VAC 2A cos 0 5 250VAC 2A 4 Electronic overload relay with manual reset and thermal memory Trip Class...

Страница 20: ...C 61000 4 5 2kV line to ground 1kV line to line IEC 61000 4 6 10V 1 NOTICE This product has been designed for environment A Use of this product in environment B may cause unwanted electromagnetic dist...

Страница 21: ...40 C 104 F Maximum Altitude 1 000m 3281ft above 1000m derate by 1 of VMX agility Ie per 100m 328ft to a maximum altitude of 2 000m 6562ft Environmental Rating Main Circuit IP00 IP20 with optional fin...

Страница 22: ...ational current Ie A 80 106 132 160 195 242 302 361 Rated conditional short circuit current Iq kA 10 10 10 10 10 18 18 18 Class J time delay fuse 1 Maximum rating Z1 A 150 200 250 300 400 450 600 600...

Страница 23: ...le Horizontally Mounted Ie kW 1 FLA HP 2 Trip Class 10 Ie AC 53a 3 5 17 F S 4 Trip Class 20 Ie AC 53a 4 19 F S 4 Trip Class 30 Ie AC 53a 4 29 F S 4 A3 230V 400V 500V A3 200V 208V 220 240V 440 480V 550...

Страница 24: ...Stellar SR35 Soft Starter Quick Start Guide First Edition 01 22 2020...

Отзывы: