Do-more H2 Series PLC Hardware User Manual, 1st Edition, Rev. F - H2-DM-M
5–24
Chapter 5: Specifications - Discrete I/O Modules
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
D2–08TA, AC Output
D2-08TA AC Output
Outputs per Module
8
Commons per Module
1 (2 I/O terminal points)
Output Type
SSR (Triac)
Operating Voltage
15–264 VAC
Peak Voltage
264VAC
ON Voltage Drop
< 1.5 VAC (>0.1 A)
< 3.0 VAC (<0.1 A)
AC Frequency
47 to 63 Hz
Minimum Load Current
10mA
Max Load Current
0.5 A/point; 4A/common
Max Leakage Current
4mA (264VAC, 60Hz)
1.2 mA (100VAC, 60Hz)
0.9 mA (100VAC, 50Hz)
Max Inrush Current
10A for 10ms
Base Power Required 5VDC
250mA
OFF to ON Response
1ms
ON to OFF Response
1ms + 1/2 cycle
Terminal Type (included)
Removable; D2-8IOCON
Status Indicator
Logic side
Weight
2.8 oz. (80g)
Fuses
1 per common, 6.3 A slow blow,
non-replaceable
ZIPLink Module
ZL-RTB20 (Feedthrough)
ZIPLink Cable
ZL-D2-CBL10 (0.5 m)
ZL-D2-CBL10-1 (1.0 m)
ZL-D2-CBL10-2 (2.0 m)
C
4
5
6
7
0
1
2
3
15-264VAC
10mA-0.5A
50/60Hz
C
D2-08TA
OUT
110-220
VAC
0
1
2
3
4
5
6
7
L
L
C
4
5
6
7
0
1
2
3
15-264VAC
10mA-0.5A
50/60Hz
C
D2-08TA
OUT
110-220
VAC
0
1
2
3
4
5
6
7
L