Do-more H2 Series PLC Hardware User Manual, 1st Edition, Rev. F - H2-DM-M
5–12
Chapter 5: Specifications - Discrete I/O Modules
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
D2-04TD1, DC Output
D2-04TD1 DC Output
Outputs per Module
4 (current sinking)
Output Points Consumed
8 points (only first 4 pts. used)
Commons per Module
1 (4 I/O terminal points)
Output Type
NMOS FET (open drain)
Operating Voltage
10.2–26.4 VDC
Peak Voltage
40VDC
ON Voltage Drop
0.72 VDC maximum
AC Frequency
N/A
Max Load Current (resistive)
4A/point
8A/common
Max Leakage Current
0.1 mA @ 40VDC
Max Inrush Current
6A for 100ms, 15A for 10ms
Minimum Load Current
50mA
External DC Required
24VDC @ 20mA max.
Base Power Required 5VDC
60mA
OFF to ON Response
1ms
ON to OFF Response
1ms
Terminal Type (included)
Removable; D2-8IOCON
Status Indicator
Logic side
Weight
2.8 oz. (80g)
Fuses
4 (1 per point)
(6.3 A slow blow, non-replaceable)
ZIPLink Module*
ZL-RTB20 (Feedthrough)
ZIPLink Cable*
ZL-D2-CBL10 (0.5 m)
ZL-D2-CBL10-1 (1.0 m)
ZL-D2-CBL10-2 (2.0 m)
*D2-04TD1 outputs are derated not to exceed 2 Amps per point and 2 Amps per
common when using the ZIPLink wiring system.
At 40mS duration, loads of 3.0 A or greater cannot be used.
At 100mS duration, loads of 2.0 A or greater cannot be used.
Find the load current you expect to use and the duration that the
output is ON. The number at the intersection of the row and column
represents the switching cycles per minute. For example, a 1A
inductive load that is on for 100 ms can be switched on and off a
maximum of 60 times per minute. To convert this to duty cycle
percentage use: (duration x cycles)/60. In this example,
(60 x 0.1)/60 = 0.1, or 10% duty cycle.
0
1
2
3
4
0
10
20
30
40
50 55
Ambient Temperature (°C/°F )
32
50
68
86
104
122131
C
°
F
°
Points
2A / Pt.
3A / Pt.
4A / Pt.
Derating Chart
0V
24V
C
C
C
C
0
1
2
3
24VDC
Internally
connected
L
L
L
L
+
12--24VDC +
Common
L
12--24
+
--
+
--
24VDC
VDC
To LE D
Optical
Isolator
0V
Output
Other
Circuits
Reg
6.3A
Inductive Load
0.1A
1400
600
0.5A
300
120
1.0A
140
60
1.5A
90
35
2.0A
70
--
Load
8000
1600
100ms
800
540
3.0A
400
270
--
--
40ms
7ms
Current
Duration of output in ON state
4.0A
200
--
--
Maximum Number of Switching Cycles per Minute
0
1
2
3
C
C
C
C
L
L
L
L
C
D2-04TD1
OUT
12-24
VDC
0
1
2
3
+24V
10.2-26.4VDC
50mA-2A
0
1
2
3
C
C
C
C
L
L
C
D2-04TD1
OUT
12-24
VDC
0
1
2
3
+24V
L
L
10.2-26.4VDC
50mA-2A