Wiring Information
The H2-CTRIO(2) module has two
independent input channels, each consisting of
four optically isolated input points (pts. 1A-1D
on common 1M and pts. 2A-2D on common
2M). The inputs can be wired to either sink or
source current.
The module has four optically isolated output
points (Y0-Y3 with isolated commons C0-C3,
respectively) that can be wired to either sink
or source current. Remember that the internal
jumpers can be used to connect the input
commons or output commons together.
NOTE:
Field device wiring must be compatible with the module configuration configured in Do-more
Designer
DC type field devices are configured to either sink or source current. This affects the wiring of
the device to the CTRIO module as seen below.
When wiring CTRIO(2) modules, please consider the following:
•
Keep encoder input wiring as short as possible
•
Route wiring to avoid any runs parallel to noisy cables.
•
Route wiring to avoid the proximity of noisy devices.
•
Use shielded, twisted pair cables, such as:
24VDC
+
-
1A
1M
Sensing Circuit
This drawing illustrates wiring that is
typical for Channel 1 terminals 1A, 1B,
1C, and 1D. The same circuitry is also
present at the corresponding
Channel 2 terminals.
The same circuitry is present at the
corresponding Channel 2 terminal.
24VDC
+
-
1A
1M
Sensing Circuit
The same circuitry is present at the
corresponding Channel 2 terminal.
This drawing illustrates wiring that is
typical for Channel 1 terminals 1A, 1B,
1C, and 1D. The same circuitry is also
present at the corresponding
Channel 2 terminals.
NPN Field Device (sink)
1
1D
1M
NC
C
Y
C1
Y1
1A
1B
C
0
0
2A
2B
2C
2D
2
C
2
Y
3
C
3
Y
M
2
+
-
+
-
+
-
+
-
L
– +
– +
L
– +
– +
L
– +
– +
L
– +
– +
CTR
IN
OK
ER
1A
2A
0
1
2
3
H2-CTRIO
+24 VDC
OUTPUTS
2A
2B
2C
2D
2M
C2
Y2
C3
Y3
1A
1B
1C
1D
1M
NC
C0
Y0
C1
Y1
IN 9-30 VDC 5-12 mA
OUT 5-36 VDC
1.0Amax
per point
PNP Field Device (source)
Suggested Cabling
Type of Cable Supplier/Part Number
Supplier/Part Number
3 pair, twisted,
overall shield
AutomationDirect/L19853-XXXX
Belden/8103
1 pair, twisted,
overall shield
AutomationDirect/L19827-XXXX
Belden/9841
H2-CTRIO(2) Wiring Considerations