Do-more H2 Series PLC User Manual, 1st Edition, Rev. F - H2-DM-M
7–8
Chapter 7: Specifications - Specialty Modules
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
H2-CTRIO(2) LED Indicators
H2-CTRIO(2) LED Descriptions
OK
Module OK
ER
User Program Error
1A
Channel 1 Status
2A
Channel 2 Status
0–3
Output Status
H2-CTRIO(2) LED Diagnostic Definition
1A/2A
Blinking 7 times per second
Input is configured as Counter and is changing
Following state of input
Input is not configured as counter
0-3
Follow actual output state: ON = output is passing current
CTR
IN
OK
ER
1A
2A
0
1
2
3
H2-CTRIO
+24 VDC
OUTPUTS
2A
2B
2C
2D
2M
C2
Y2
C3
Y3
1A
1B
1C
1D
1M
NC
C0
Y0
C1
Y1
IN 9-30 VDC 5-12 mA
OUT 5-36 VDC
1.0Amax
per point
CTR
IN
OK
ER
1A
2A
0
1
2
3
H2-CTRIO2
+24 VDC
OUTPUTS
2A
2B
2C
2D
2M
C2
Y2
C3
Y3
1A
1B
1C
1D
1M
NC
C0
Y0
C1
Y1
IN 9-30 VDC 5-12 mA
OUT 5-36 VDC
1.0Amax
per point
H2-CTRIO(2) LED Diagnostic Definitions
LED OK
LED ER
Description
Blinking
Blinking
Boot Mode - Used for Field OS Upgrades
Blinking
OFF
Program Mode
OFF
Blinking
Module Self-Diagnostic Failure
(Blinks may be coded by counts)
OFF
ON
Module Error Due to Watchdog Timeout
OFF
OFF
No Power to Module
ON
OFF
All is well - RUN Mode
ON
ON
Hardware Failure (H2-CTRIO)
Not Used (H2-CTRIO2)