Part Number Key

AutomationDirect.com (ADC)

3505 Hutchinson Road, Cumming, GA 30040

Phone: (800) 633-0405 or (770) 889-2858

ACS200 SERIES

INSTALLATION 

INSTRUCTIONS

Quick Start Guide

1.  

Run the wire to be monitored through the 

aperture.

2.  Mount the sensor or suspend on conductor.

3.  Connect output wiring. 

a. Use 22-14AWG copper conductors rated 

75˚C min only and tighten terminals to 9 

in-lbs torque. 

b. Make sure the load matches the output 

shown on the sensor’s label (volts, amps,  

AC/DC).

4.  

Adjust setpoint. 

a. Choose correct range by positioning the 

Range Jumper. 

b. Use the potentiometer to adjust the 

setpoint. 

5.  Confirm Contact Operation. 

If the sensor has an LED, a quick flash indi-

cates current over the setpoint and output 

has tripped; slow flash shows current under 

setpoint; output is shelf state condition.

 

F - Fixed Core (terminals on the side)

 

S - Solid Core (terminals on the top)

 

 

 

A C S  200 -  A    D         -   F        

SENSOR TYPE:

Switch

AC monitored current

SERIES 

A - AC

D - DC

OUTPUT (Solid State Switch)

CASE STYLE

OUTPUT TYPE

 

A - Normally Open

C - Normally Closed

   

  

      

OUTPUT RATING

 

Blank - 1A 240VAC or 0.15 A @ 30VDC

3        - 3A at 120VAC

FT - Fixed Core (terminals on top)

®

ACS200 - Inst - Rev 4     0820  P-N 391000212

Specifications

Power Supply

None - self powered

Output

Isolated solid-state switch

Switch Rating

DC Output Type: 0.15A @ 30VDC

AC Output Type: 1.0A @ 240VAC. 

-AA3 model: 3A @ 120VAC

Off State Leakage

<10µA AC or DC N.O., 2.5mA AC N.C., 1.4mA DC 

N.C.

Response Time

40 to 250 ms

Hysteresis

5%

Input Ranges

Fixed core: 1-6, 6-40 & 40-175 A 

Split core: 1.75-6, 6-40 & 40-200 A

Setpoint Adjust

4 Turn potentiometer, 15 Turn potentiometer  

-FT Case Style

Isolation Voltage

UL tested to 1480VAC

Frequency Range

6 to 100 Hz

Sensing Aperture

-F Case Style: 0.55 in (14mm) dia.

-S Case Style: 0.85 in (21.7 mm) sq.

-FT Case Style: 0.75 in (19mm) dia.

Case

UL 94V-0 Flammability rated thermoplastic

Environmental 

-Temp -4 to 122°F (-20 to 50°C), 104°F (40°C) 

max for model ending in -03

-Humidity 0-95% RH, Non-condensing

-Pollution degree 2

-Altitude 2000 meters

Certifications

cULus listed E222847

CE

Sensed Current Limit

Range 

Jumper

Range 

Fixed 

Core

Range 

Split 

Core

Continuous Max. 6 

Seconds

Max.1 

Second

None

1 - 6A

1.75 - 6A

200A

400A

600A

Mid

6 - 40A

6 - 40A

200A

500A

800A

High

40 - 175A

40 - 200A

200A

800A

1200A

Warning! Risk of electric shock or 

personal injury

Safe operation can only be guaranteed if the 
device is used for the purpose for which it was 
designed and within the limits of the technical 
specifications. When this symbol is used, it 
means you should consult all documentation to 
understand the nature of potential hazards and 
the action required to avoid them.

Warning! Risk of hazardous voltage

When operating the device, certain parts may 
carry hazardous live voltage (e.g., primary 
conductor, secondary terminals). The device 
should not be put into service if the installation 
is not complete.

For products intended for the EU market, the  

following is applicable to the CE compliance of 

the product:

The ACS200 Series may comply with EN 61010-1 CAT III 
300V max line-to-neutral measurement category. If insulated 
cable is used for the primary circuit, the voltage rating of the 
measurement category can be improved according to the 
characteristics given by the cable manufacturer.