Part Number Key
AutomationDirect.com (ADC)
3505 Hutchinson Road, Cumming, GA 30040
Phone: (800) 633-0405 or (770) 889-2858
ACS200 SERIES
INSTALLATION
INSTRUCTIONS
Quick Start Guide
1.
Run the wire to be monitored through the
aperture.
2. Mount the sensor or suspend on conductor.
3. Connect output wiring.
a. Use 22-14AWG copper conductors rated
75˚C min only and tighten terminals to 9
in-lbs torque.
b. Make sure the load matches the output
shown on the sensor’s label (volts, amps,
AC/DC).
4.
Adjust setpoint.
a. Choose correct range by positioning the
Range Jumper.
b. Use the potentiometer to adjust the
setpoint.
5. Confirm Contact Operation.
If the sensor has an LED, a quick flash indi-
cates current over the setpoint and output
has tripped; slow flash shows current under
setpoint; output is shelf state condition.
F - Fixed Core (terminals on the side)
S - Solid Core (terminals on the top)
A C S 200 - A D - F
SENSOR TYPE:
Switch
AC monitored current
SERIES
A - AC
D - DC
OUTPUT (Solid State Switch)
CASE STYLE
OUTPUT TYPE
A - Normally Open
C - Normally Closed
OUTPUT RATING
Blank - 1A 240VAC or 0.15 A @ 30VDC
3 - 3A at 120VAC
FT - Fixed Core (terminals on top)
®
ACS200 - Inst - Rev 4 0820 P-N 391000212
Specifications
Power Supply
None - self powered
Output
Isolated solid-state switch
Switch Rating
DC Output Type: 0.15A @ 30VDC
AC Output Type: 1.0A @ 240VAC.
-AA3 model: 3A @ 120VAC
Off State Leakage
<10µA AC or DC N.O., 2.5mA AC N.C., 1.4mA DC
N.C.
Response Time
40 to 250 ms
Hysteresis
5%
Input Ranges
Fixed core: 1-6, 6-40 & 40-175 A
Split core: 1.75-6, 6-40 & 40-200 A
Setpoint Adjust
4 Turn potentiometer, 15 Turn potentiometer
-FT Case Style
Isolation Voltage
UL tested to 1480VAC
Frequency Range
6 to 100 Hz
Sensing Aperture
-F Case Style: 0.55 in (14mm) dia.
-S Case Style: 0.85 in (21.7 mm) sq.
-FT Case Style: 0.75 in (19mm) dia.
Case
UL 94V-0 Flammability rated thermoplastic
Environmental
-Temp -4 to 122°F (-20 to 50°C), 104°F (40°C)
max for model ending in -03
-Humidity 0-95% RH, Non-condensing
-Pollution degree 2
-Altitude 2000 meters
Certifications
cULus listed E222847
CE
Sensed Current Limit
Range
Jumper
Range
Fixed
Core
Range
Split
Core
Continuous Max. 6
Seconds
Max.1
Second
None
1 - 6A
1.75 - 6A
200A
400A
600A
Mid
6 - 40A
6 - 40A
200A
500A
800A
High
40 - 175A
40 - 200A
200A
800A
1200A
Warning! Risk of electric shock or
personal injury
Safe operation can only be guaranteed if the
device is used for the purpose for which it was
designed and within the limits of the technical
specifications. When this symbol is used, it
means you should consult all documentation to
understand the nature of potential hazards and
the action required to avoid them.
Warning! Risk of hazardous voltage
When operating the device, certain parts may
carry hazardous live voltage (e.g., primary
conductor, secondary terminals). The device
should not be put into service if the installation
is not complete.
For products intended for the EU market, the
following is applicable to the CE compliance of
the product:
The ACS200 Series may comply with EN 61010-1 CAT III
300V max line-to-neutral measurement category. If insulated
cable is used for the primary circuit, the voltage rating of the
measurement category can be improved according to the
characteristics given by the cable manufacturer.