Recipient Device Object
Identifier
Type the
Device Instance
from SiteBuilder (or from the
network administrator for third-party devices) in the
#
field.
Process Identifier
Change for third-party devices that use a BACnet Process
Identifier other than 1. WebCTRL processes alarms for any
32-bit Process Identifier.
Issue Confirmed
Notifications
Select to have a device continue sending an alarm
message until it receives delivery confirmation from the
recipient.
Calendars are provided in the driver for BACnet compatibility only. Use WebCTRL's
Schedules
feature instead.
On these pages, you can enable/disable, change BACnet alarm properties, or set delays
for the following BACnet alarms:
Common alarms:
Specific alarm:
•
Module Halted
•
All Programs Stopped
•
Duplicate Address
•
Locked I/O
•
Control Program
•
Program Stopped
•
Excessive COV
•
Low Battery Alarm
NOTE
To set up alarm actions for controller generated alarms, see
Setting up alarm
actions
in WebCTRL Help.
Module Generated Alarm
Description
Short message shown on WebCTRL's Alarm page or in an
alarm action when this type of alarm is generated.
Events
Alarm Category and
Alarm Template
See
Customizing alarms
in WebCTRL Help.
Enable
Clear these checkboxes to disable Alarm or Return to
normal messages of this type from this controller.
Notification Class
Do not change this field.
You can set up a translation table that an analog input will use to translate the raw data
from a non-linear sensor to the engineering units you want it to output on the wire. In the
NET
tree, select
Custom Translation Table #1
,
#2
, or
#3
. The
Properties
page has
instructions. For the input to use the translation table, navigate to the input in WebCTRL's
GEO
tree, select the
Details
tab, then set
Sensor Type (Scaling Method)
to
Non-Linear,
Custom Table #__
.
Calendars
Common and
Specific Alarms
Custom
Translation
Tables