Input wiring
Input
Maximum length
Minimum gauge
Shielding
Thermistor
Dry contact
1000 feet
(305 meters)
22 AWG
Shielded
0–5 Vdc
1000 feet
(305 meters)
26 AWG
Shielded
Output wiring
To size output wiring, consider the following:
•
Total loop distance from the power supply to the controller, and then to the controlled
device
NOTE
Include the total distance of actual wire. For 2-conductor wires, this is twice the
cable length.
•
Acceptable voltage drop in the wire from the controller to the controlled device
•
Resistance (Ohms) of the chosen wire gauge
•
Maximum current (Amps) the controlled device requires to operate
1
Verify that the Room Controller's power and communications connections work
properly.
2
Remove power from the Room Controller.
3
Connect the input wiring to the screw terminals on the Room Controller.
Wiring inputs and outputs
Wiring
specifications
To wire inputs
and outputs