The table below outlines the limitations and
requirements depending on whether you are
using WebCTRL or SuperVision to
communicate with your InterOP8500.
For more information, see the appropriate
module driver document on the Automated
Logic website at www.automatedlogic.com.
Specifications
Power
5VDC, 175mA (external), 275 mA
(internal).
12VDC, 25mA.
12VDC, 175mA (external power), 25 mA
(internal power) supplied through the
card-edge connector.
24VAC, 300mA for use with the large
keypad/display.
Inputs
8 binary inputs, 15 analog inputs
(configurable for 1k ohm nickel RTD or 1
to 5V).
Input Resolution
12 bit A/D.
Digital Outputs
16 digital outputs,
12VDC, 300mA fused output.
Communication
For WebCTRL, 156 kbps
BACnet-over-ARCNET and 9600 bps or
38.4 kbps EIA-485 BACnet MS/TP.
For SuperVision, 156 kbps BACnet-over-
ARCNET, 9600 bps or 38.4 kbps Legacy
CMnet. Access Port:9600 bps or 38.4 kbps
EIA-485.
WebCTRL
SuperVision
Module Driver
DRV_InterO
P8500
85M
Number of Function
Blocks*
100
59
Number of BACnet
Objects*
2000
1000
* depending on available memory
Figure 2. Network Architecture
Johnson Field
Termination Board
Johnson
Field Device
Johnson
Field Device
Johnson
Field Device
Johnson I/O Devices
Johnson
Field Device
InterOp8500
CMnet (ARC156)
U-Cards
UNI/32
U-Line: 9600 bps or 38400 bps
TNPB
MX-Line
LGRM-E
MX-Line
S-Line
For WebCTRL, BACnet/IP.
For SuperVision, BACnet/Ethernet.