TrueAlert ES Addressable US/Weather Proof Ceiling Mount Speaker Notification Appliances Installation
Instructions
To Access Switches:
SO Appliance
S/V Appliance
ALARM/
ALERT
001
101
011
111
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
DIP SWITCHES 5 THROUGH
7
000
100
010
110
Figure 5: Setting the DIP switch address
Setting the strobe candela setting
1.
The jumpers are factory set to FACP. Use this setting when programming the candela setting at the 4100ES FACP. The candela setting is visible
through the slot on the side of the appliance.
2.
For manual selection, remove the cover and slide the candela flag to the required setting:
W75, W110, W185, 110 candela, or FACP.
The candela setting is visible through the slot on the side of the appliance.
Note:
To avoid a programming mismatch trouble, an authorized service personnel must program one of the four candela outputs for each appliance.
To set the candela through the Programmer, set it to FACP. For additional information refer to the
4100ES Programmer’s Manual
(574-849AC).